Power source requirements
The BladeCenter S system can run on either 110 V ac or 220 V ac. Each of the four power supplies in the BladeCenter S chassis is capable of handling either type of power source.
Note
Although the power modules are autoranging and can support either 110 V ac or 220 V ac, you cannot mix voltage power sources within the same BladeCenter S system. All power modules within a BladeCenter S system must be connected to either a 110 V ac or 220 V ac power sources.
AC power input must be adequate to supply the required voltage and amperage at an input frequency range from 50-60 hertz (Hz). The BladeCenter S system requires the following ac input voltage:
Nominal Voltage | Minimum Voltage | Maximum Voltage |
---|---|---|
110 V ac | 100 | 127 |
220 V ac | 200 | 240 |
The ac input current requirements are shown in the following table:
Nominal Voltage | Nominal Amps | Maximum Continuous Amps |
---|---|---|
100 V ac | 11.2 | 13.9 |
200 V ac | 8.0 | 9.0 |
Give documentation feedback