Completing the replacement process

After you replace the part, you can return the failed part to Lenovo, as described in the RMA instructions shipped with the kit.Contact technical support at Lenovo Data Center Support if you need the RMA number or additional help with the replacement procedure.
  1. Recable the system storage and networking cables, as needed.
  2. Reconnect the power supply.
    1. Open the power cable retainer and plug the power cable into the power supply.
    2. Plug the power cable into the power source.
  3. Return the node to normal operation by giving back its storage from the running node: storage failover giveback -ofnode impaired_node_name
    Note
    This operation need to be performed when the impaired node shows "Waiting for giveback...".
  4. If automatic giveback was disabled, reenable it: storage failover modify -node local -auto-giveback true