Size (10U)

  • Height: 440 mm (17.32 in.)
  • Depth: 830 mm (32.68 in.)
  • Width: 447 mm (17.6 in.)
  • Weight:
    • Fully configured (stand-alone): approximately 220.4 kg (486.1 lb)
    • Fully configured (in the rack): approximately 225.6 kg (497.4 lb)
    • Empty chassis with shelves: approximately 65.7 kg (145 lb)
    • Empty chassis without shelves: approximately 44.4 kg (98 lb)

Node bays (front)

The chassis comes with fourteen node bays on the front that can physically contain the following:
  • Up to fourteen 1-bay compute nodes.
    Note

    The exact maximal number of supported 1-bay nodes is determined by input voltage and power redundancy policy. See the following table for detailed combinations, or alternatively, refer to Lenovo Capacity Planner for more details.

    See the following tables for limited maximal number of different nodes that are supported in the same chassis.

    Table 1. Limited maximal number of SN550 in the same chassis
    2500 W power output (200-208 V ac)2745 W power output (200 or higher V ac)
    Processor TDP
    • N+1
    • N=3
    • 4 PSUs
    • with throttling
    • N+N
    • N=3
    • 6 PSUs
    • with throttling
    • N+N
    • N=3
    • 6 PSUs
    • without throttling
    • N+N
    • N=3
    • 6 PSUs
    • without throttling
    85 W14141213
    105 W14141112
    125 W14141011
    130 W14141011
    140 W1314910
    150 W1314910
    165 W121389
    Table 2. Limited maximal number of SN550 V2 in the same chassis
    2500 W power output (200-208 V ac)
    Processor TDP
    • N+1
    • N=4
    • 5 PSUs
    • With throttle
    • N+1
    • N=3
    • 4 PSUs
    • With throttle
    • N+N
    • N=3
    • 6 PSUs
    • With throttle
    • N+1
    • N=5
    • 6 PSUs
    • No throttle
    • N+N
    • N=3
    • 6 PSUs
    • No throttle
    105 W141414149
    120 W141314148
    135 W141213138
    140 W141213138
    150 W141212127
    165 W141111127
    185 W131010116
    195 W1399106
    205 W1399106
    230W129995
    2745 W power output (220-240 V ac)
    Processor TDP
    • N+1
    • N=4
    • 5 PSUs
    • With throttle
    • N+1
    • N=3
    • 4 PSUs
    • With throttle
    • N+N
    • N=3
    • 6 PSUs
    • With throttle
    • N+1
    • N=5
    • 6 PSUs
    • No throttle
    • N+N
    • N=3
    • 6 PSUs
    • No throttle
    105 W1414141410
    120 W141314149
    135 W141213149
    140 W141213149
    150 W141212138
    165 W141111138
    185 W141111127
    195 W141010116
    205 W141010116
    230W1399106
  • Up to seven 2-bay compute nodes (with the shelves removed from the chassis)
  • Up to three 4-bay storage nodes or enclosures (with the shelves removed from the chassis)
  • Mixing of 1-bay, 2-bay and 4-bay nodes (with the shelves removed from the chassis)

Device capacity (rear)

The chassis comes with the following bays on the rear:
  • Two hot-swap Chassis Management Module bays
  • Six hot-swap power-supply bays
  • Ten hot-swap fan bays
  • Four hot-swap I/O bays
  • Two hot-swap fan logic bays

Upgradeable microcode

Microcode is upgradeable when fixes or features are added.
  • Flex System Manager management node firmware
  • Chassis Management Module firmware
  • I/O module firmware
  • Compute node firmware

Security features

  • Login password for remote connection
  • Secure Sockets Layer (SSL) security for remote management access
  • Lightweight Directory Access Protocol (LDAP)
  • Trusted and signed firmware

Predictive Failure Analysis (PFA) alerts

  • Power supplies
  • Node dependent features

Electrical input

  • Rated voltage and frequency 200 - 240 V ac single phase at 47-63 Hz
  • Inrush current (chassis maximum) 40 A
  • Leakage current (chassis maximum) 580 uA
  • Branch circuit breaker 20 A maximum

Power supplies

  • Minimum: Two hot-swap power supplies
  • Maximum: Six hot-swap power supplies
  • Available with 2100 Watt or 2500 Watt, 200 - 240 V ac power supplies (IEC 60320 type C20 line cord connector)
  • Available in certain markets with 2500 Watt, 240 - 380 V dc power supplies (RF-203 line cord connector)
  • Optional 2500 Watt, -48 to -60 V dc power supplies (2 position power connector)

Fan

Up to 10 variable-speed, hot-swap fan modules are supported, including the following:
  • Two 40 mm fan modules
  • Up to eight 80 mm fan modules

Management modules

Two hot-swap Chassis Management Modules

I/O modules

Supports up to four scalable switch modules with each providing a 4-lane physical interconnect.

Heat output

  • Approximate heat output:
    • Minimum configuration: 1365 Btu per hour (400 watts)
    • Maximum configuration: 44,017 Btu per hour (12,900 watts)

  • Declared sound power level: 7.5 bels
  • Chassis airflow: Full chassis configuration with all nodes, I/O modules, power supplies, and fan modules installed.
    • Minimum - 270 CFM
    • Maximum - 1,020 CFM

Environment:

The Flex System Enterprise Chassis complies with ASHRAE class A3 specifications.
  • Power on 1:
    • Temperature: 5°C - 40°C (41°F - 104°F) 3
    • Humidity, non-condensing: -12°C dew point (10.4°F) and 8% - 85% relative humidity 5,6
    • Maximum dew point: 24°C (75°F)
    • Maximum altitude: 3048 m (10,000 ft)
    • Maximum rate of temperature change: 5°C/hr (41°F/hr ) 4
  • Power off 2:
    • Temperature: 5°C to 45°C (41°F - 113°F)
    • Relative humidity: 8% - 85%
    • Maximum dew point: 27°C (80.6°F)
  • Storage (non-operating):
    • Temperature: 1°C to 60°C (33.8°F - 140°F)
    • Altitude: 3050 m (10,006 ft)
    • Relative humidity: 5% - 80%
    • Maximum dew point: 29°C (84.2°F)
  • Shipment (non-operating) 3:
    • Temperature: -40°C to 60°C (-40°F - 140°F)
    • Altitude: 10,700 m (35,105 ft)
    • Relative humidity: 5% - 100%
    • Maximum dew point: 29°C (84.2°F) 8
1 Chassis is powered on.
2 Chassis is removed from original shipping container and is installed but not in use, for example, during repair, maintenance, or upgrade.
3 The equipment acclimation period is 1 hour per 20°C of temperature change from the shipping environment to the operating environment.