Install a DWC PSU

Use this information to install a DWC PSU.

About this task
S001
shock hazard
DANGER
danger
Electrical current from power, telephone, and communication cables is hazardous.

To avoid a shock hazard:

  • Connect all power cords to a properly wired and grounded electrical outlet/source.
  • Connect any equipment that will be attached to this product to properly wired outlets/sources.
  • When possible, use one hand only to connect or disconnect signal cables.
  • Never turn on any equipment when there is evidence of fire, water, or structural damage.
  • The device might have more than one power cord, to remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S035
shock hazard
CAUTION

Never remove the cover on a power supply or any part that has this label attached. Hazardous voltage, current, and energy levels are present inside any component that has this label attached. There are no serviceable parts inside these components. If you suspect a problem with one of these parts, contact a service technician.

CAUTION


High touch current. Connect to earth before connecting to supply.
Attention
  • Read Installation Guidelines and Safety inspection checklist to ensure that you work safely.

  • The following notes describe the type of power supply that the enclosure supports and other information that you must consider when you install a power supply:
    • Make sure you follow the guidelines in PSU configuration.

    • For redundancy support, you must install an additional hot-swap power supply or DWC PSU, if one is not installed in your model.
    • Make sure that the devices that you are installing are supported. For a list of supported optional devices for the enclosure, see Lenovo ServerProven website.
Watch the procedure
  • A video of this procedure is available at YouTube.

Procedure

  1. If a DWC PSU shipping bracket is installed; after final rack placement, remove the four screws and remove the DWC PSU shipping bracket.
    Figure 1. DWC PSU shipping bracket removal
    DWC PSU shipping bracket removal
  2. Install the DWC power supply.
    1. Slide the DWC power supply into the bay until it stops.
    2. Rotate the cam handles inwards to secure the DWC power supply in place.
    Important
    During normal operation, each power-supply bay must contain either a power supply or power-supply filler panel for proper cooling.
    Figure 2. DWC power supply installation
    DWC power supply installation
  3. Connect the DWC PSU manifold hose assembly to the DWC power supply quick connect.
    Figure 3. DWC PSU hose assembly installation
    DWC PSU hose assembly installation
  4. Connect one end of the power cords for the power supply into the AC connector on the back of the power supply; then, connect the other end of the power cords into a properly grounded electrical outlet.
  5. If the node is turned off, turn on the node.
  6. Make sure that the AC power LED on the power supply is lit, indicating that the power supply is operating correctly. If the solution is turned on, make sure that the dc power LED on the power supply is lit also.
After you finish
  1. Reconnect the power cords and any cables that you removed.

  2. Turn on all compute nodes.