Remove a DWC PSU

Use this information to remove a DWC PSU.

About this task

S001
shock hazard
DANGER
danger
Electrical current from power, telephone, and communication cables is hazardous.

To avoid a shock hazard:

  • Connect all power cords to a properly wired and grounded electrical outlet/source.
  • Connect any equipment that will be attached to this product to properly wired outlets/sources.
  • When possible, use one hand only to connect or disconnect signal cables.
  • Never turn on any equipment when there is evidence of fire, water, or structural damage.
  • The device might have more than one power cord, to remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S002
disconnect all power
CAUTION
The power-control button on the device and the power switch on the power supply do not turn off the electrical current supplied to the device. The device also might have more than one power cord. To remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S035
shock hazard
CAUTION

Never remove the cover on a power supply or any part that has this label attached. Hazardous voltage, current, and energy levels are present inside any component that has this label attached. There are no serviceable parts inside these components. If you suspect a problem with one of these parts, contact a service technician.

CAUTION


High touch current. Connect to earth before connecting to supply.
Attention
  • Read Installation Guidelines and Safety inspection checklist to ensure that you work safely.

  • Disconnect the power cord from the connector on the back of the power supply.

  • If only one DWC PSU is installed in the solution, you must turn off the solution before removing the power supply.

Watch the procedure
  • A video of this procedure is available at YouTube.

Procedure

  1. Disconnect the power cords from the electrical outlet; then, disconnect the other end of the power cords from the back of the power supply.
  2. Disconnect the DWC PSU manifold hose assembly from the DWC power supply quick connect.
    Figure 1. DWC PSU hose assembly removal
    DWC PSU hose assembly removal
  3. Remove the DWC power supply.
    1. Rotate the cam handles outwards, the DWC PSU will move slightly out of the bay.
    2. Grasp the handle and pull the DWC power supply out of the bay.
    Figure 2. DWC power supply removal
    DWC power supply removal
After you finish

If you are instructed to return the component or optional device, follow all packaging instructions, and use any packaging materials for shipping that are supplied to you.

To drain the DWC power supply, follow the instructions below:
  1. Place the DWC power supply standing upright (Inlet top, Outlet bottom) on an elevated flat surface.

  2. Make sure the valve on the hose assembly (supplied to customer installation site) is closed (valve handle perpendicular to the hose); then, connect the hose to Outlet quick connect and place the other end in the bucket. Slowly open the hose valve to allow water to flow out of the hose. Close the hose valve once water stops flowing.

    Figure 3. DWC power supply removal
    DWC power supply removal
  3. Disconnect the hose assembly from Outlet quick connect and connect it to Inlet quick connect; then, turn the DWC power supply upside down (Outlet top, Inlet bottom). Slowly open the hose valve to allow water to flow out of the hose. Close the hose valve once water stops flowing.

    Figure 4. DWC power supply removal
    DWC power supply removal
  4. Disconnect the hose assembly.