ASHRAE class compliance information
Air temperature:
Operating:
ASHRAE class A2: 10–35°C (50–95°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient temperature value decreases by 1°C (1.8°F) with every 300 m (984 ft) of altitude increase.
ASHRAE class A3: 5–40°C (41–104°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient temperature value decreases by 1°C (1.8°F) with every 175 m (574 ft) of altitude increase.
ASHRAE class A4: 5–45°C (41–113°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient temperature value decreases by 1°C (1.8°F) with every 125 m (410 ft) of altitude increase.
Server off: 5–45°C (41–113°F)
Shipping or storage: -40–60°C (-40–140°F)
Maximum altitude: 3050 m (10 000 ft)
Relative humidity (non-condensing):
- Operating:
ASHRAE class A2: 8%–80%; maximum dew point: 21°C (70°F)
ASHRAE class A3: 8%–85%; maximum dew point: 24°C (75°F)
ASHRAE class A4: 8%–90%; maximum dew point: 24°C (75°F)
Shipping or storage: 8%–90%
No NVMe drive, M.2 drive, middle bay, rear bay, GPU adapter, Ethernet adapter of 10 GbE or higher, or PCIe SSD adapter is installed.
- Required processor TDP for supported server models:
TDP ≤ 120 watts for server model with 24 x 2.5-inch front drive bays
TDP ≤ 155 watts for server model with 8 x 3.5-inch, 8 x 2.5-inch, or 16 x 2.5-inch front drive bays