Install 48U Advanced Rack Extension Kit
See this topic to learn how to install 48U Advanced Rack Extension Kit.
Note
Each unit of rack extension kit comes with additional capacity for up to two 0U PDUs, or one 0U PDU and one manifold, on each side of the rack.
Each rack cabinet supports up to two units of rack extension kit (one to the front and one to the rear side).
If there is a plan to install baying kit while only one of the adjacent cabinets will be installed with extension, make sure to install the baying kit first (see Install the baying kit). Then, as preparation for this procedure, remove the two screws from the upper and lower part of the cabinet that will be installed with the extension kit, and jump to Step 2.
Figure 1. Removing screws to prepare for extension installation- Required tools
- One tool with plastic blade/scissors to open the packaging
- One rubber hammer to align the extension panels with the side of the rack
- One Screwdriver with No. 3 Phillips bit to tighten the M6 screws (9 in the next bullet point)
- One Nut-driver with holding hex bit 10 mm to tighten the M6 screws (9 in the next bullet point)
- One 2.5 mm Hex bit socket to tighten the M4 screws (13 in the next bullet point)
- One 3 mm Hex bit socket to tighten the M5 screws (PDU/manifold brackets, opening covers on the extension panels)
- One 4 mm Hex bit socket to tighten the M6 screws (3 and 12 in the next bullet point)
- The extension kit comes with a miscellaneous bag, which contains the following components:Figure 2. Parts
No. Description Quantity No. Description Quantity 1 Left extension panel 1 8 M6 cage nut 14 2 Support bracket 3 9 M6 x 16 mm hex head flange screw 14 3 M6 x 12 mm flat head socket cap screw 12 10 Cable strap module 123 2 4 Doorstop 2 11 Grounding plate 5 5 Door latch 1 12 M6 x 16 mm flat head socket cap screw 2 6 Right extension panel 1 13 M4 x 6 mm flat head socket cap screws 4 7 Extension top cover 1 14 Grounding wire 4 3 - 1 Cable straps are removable, remove the straps from the extension panels if needed.
- 2 Cable straps can be lengthened by connecting two or more straps together.
- 3 Use cable straps to secure PDUs and manifolds prior to shipping.
- 4 Connect one end of the grounding wire to the grounding plate on the extension panel and the other end to the nearest grounding plate on the rack.
Figure 3. Hex Allen wrenchesNo. Description 1 Hex Allen wrench, 4 mm 2 Hex Allen wrench, 3 mm 3 Hex Allen wrench, 2.5 mm
Procedure