Features and specifications
Use this information to view specific information about the compute node, such as compute node hardware features and the dimensions of the compute node.
The following table is a summary of the features and specifications of the Lenovo Flex System x240 M5 compute node.
Note
- Power, cooling, and chassis systems management are provided by the Lenovo Flex System chassis.
- The operating system in the compute node must provide USB support for the compute node to recognize and use USB media drives and devices. The Lenovo Flex System chassis uses USB for internal communication with these devices.
Features and specifications | |
Microprocessor: Up to two multi-core Intel Xeon microprocessors. Note Use the Setup utility to determine the type and speed of the microprocessors in the compute node. Integrated functions:
Memory:
Predictive Failure Analysis (PFA) alerts:
Drives:
Upgradeable firmware: All firmware is field upgradeable. | Size:
Environment: The Lenovo Flex System x240 M5 compute node complies with ASHRAE class A3 specifications.
Security:
|
- Chassis is powered on.
- A3 - Derate maximum allowable temperature 1°C/175 m above 950 m.
- The minimum humidity level for class A3 is the higher (more moisture) of the -12 °C dew point and the 8% relative humidity. These intersect at approximately 25°C. Below this intersection (~25C), the dew point (-12 °C) represents the minimum moisture level; above the intersection, relative humidity (8%) is the minimum.
- Moisture levels lower than 0.5°C DP, but not lower -10 °C DP or 8% relative humidity, can be accepted if appropriate control measures are implemented to limit the generation of static electricity on personnel and equipment in the data center. All personnel and mobile furnishings and equipment must be connected to ground via an appropriate static control system. The following items are considered the minimum requirements:
- Conductive materials (conductive flooring, conductive footwear on all personnel who go into the datacenter; all mobile furnishings and equipment will be made of conductive or static dissipative materials).
- During maintenance on any hardware, a properly functioning wrist strap must be used by any personnel who contacts IT equipment.
- 5°C/hr for data centers employing tape drives and 20°C/hr for data centers employing disk drives.
- Chassis is removed from original shipping container and is installed but not in use, for example, during repair, maintenance, or upgrade.
- The equipment acclimation period is 1 hour per 20°C of temperature change from the shipping environment to the operating environment.
- Condensation, but not rain, is acceptable.