Installing the compute node cover

Use this information to install the compute node cover.

Before you install the compute node cover, read Safety and Installation guidelines.

If you are replacing the cover, make sure that you have the system service label kit on hand for use during the replacement procedure (see Parts listing, Types 7162 and 2588).

Attention
You cannot insert the compute node into the Flex System chassis until the cover is installed and closed. Do not attempt to override this protection.
Statement 21
Graphic illustrating Safety Statement 21
CAUTION
Hazardous energy is present when the compute node is connected to the power source. Always replace the compute node cover before installing the compute node.

To install the compute node cover, complete the following steps:

  1. Carefully lay the compute node on a flat, static-protective surface, orienting the compute node with the bezel pointing toward you.
  2. Orient the cover so that the posts on the inside of the cover slide into the slots on the compute node.
    Note
    Before you close the cover, make sure that the air baffles and all components are installed and seated correctly and that you have not left loose tools or parts inside the compute node.

    Graphic illustrating closing the compute node cover
  3. Hold the front of the compute node and slide the cover forward to the closed position, until it clicks into place.
  4. To install a system service label, align the label on the cover, remove the backing, and press the label on the cover.
After you install the compute node cover, install the compute node into the chassis (see Installing a compute node in a chassis for instructions).