Replacing a power supply unit (PSU)
The Lenovo Converged HX Series appliances use two power supply units. If you are using 208V input power, the two power supplies are redundant. One power supply can meet the needs of the node. Although losing one of the two power supplies does not impact the operation of a node, you should replace a failed power supply unit as soon as possible to restore redundancy.
Orange warning LED on node front panel is on.
Lenovo XClarity Administrator shows a power supply alert.
Nutanix Prism web console shows a power supply alert.
If using VMware ESXi, the vSphere client Hardware Status tab shows a power supply alert.
The Lenovo Converged HX Series appliances contain two power supplies. Identify the failed power supply by checking in Prism, XClarity Administrator or the indicator lights on the power supply units.
Disconnect the power cable for the power supply to be replaced being careful not to dislodge the other power cable.
Remove the power supply as described in Removing a hot-swap ac power supply.
Replace the power supply as described in Replacing a hot-swap ac power supply.
Reconnect the power cable.
- Verify that the power supply has been successfully replaced by checking the following:
Orange warning light on the server front panel is extinguished.
Verify indicator lights on the power supply (two green LEDs).
No error shown in Lenovo XClarity Administrator
No error shown in Prism