Skip to main content

SD650-I V3 high-density server

Refer to this section to for a brief introduction on the DW612S enclosure configuration with six SD650-I V3 server.

For more information on SD650-I V3 high-density server, see SD650-I V3 User Guide.

Attention

Start with slot 1 when installing trays into the DW612S enclosure.

Figure 1. DW612S enclosure with six SD650-I V3 server
DW612S enclosure with six SD650-I V3 server
Note
  • The illustration in this section is for reference only.

  • The slot numbers are indicated on both sides of the enclosure.

Table 1. DW612S enclosure with six SD650-I V3 server
Number of SD650-I V3 serverPower supply configurations
Six
  • Supports nine hot-swap 2400W or 2600W AC power supplies.
    • Sine-wave input (50-60 Hz) required

    • Input voltage for 2400W power supplies:

      • 200-240 Vac, 240 Vdc

    • Input voltage for 2600W power supplies:

      • 200-208 Vac, 240 Vdc (output up to 2400W only)

      • 208-240 Vac, 240 Vdc

    • Nine power supplies: 8+1 without oversubscription

    • 2400W AC power supplies is Delta only.

    Note

    Mixing PSUs manufactured by different vendors is not supported.

  • Supports three hot-swap DWC 7200W power supplies.

    • Input voltage:

      • 200-208 Vac (work as 6900W)

      • 220-240 Vac, 240 Vdc (work as 7200W)

    • Three DWC PSUs: work as 8+1 without oversubscription.

CAUTION