Replacing the chassis midplane
(Trained service technician only) Use these instructions to install the chassis midplane in the NeXtScale nx360 M5 water-cooled technology tray.
To install the chassis midplane, complete the following steps.
- Slide the enclosure into the rack. Figure 4. Sliding the enclosure 
- Reinstall two EIA covers at the front of the enclosure; then, reinstall eight screws. Figure 5. EIA cover installation 
- Reinstall eight screws to secure two support brackets on the rear enclosure.Figure 6. Support bracket installation 
- Reinstall eight screws (using the screwdriver contained in the manifold repair kit) to secure two manifolds. Figure 7. Manifold screw locations - Table 1. Manifold screw locations - 1 Screws - 2 Manifold 
- Reinstall all power supplies back to the enclosure. Figure 8. Hot-swap power supply installation 
- Reinstall the blank filler. Figure 9. Blank filler installation 
- Reinstall FPC card module support bracket and FPC card module. Figure 10. Support bracket installation Figure 11. FPC card module installation Figure 11. FPC card module installation 
- Reinstall manifold retention brackets that are retaining the manifolds (top enclosure position only). Figure 12. Retention bracket installation 
- Align the drip sensor assembly with the enclosure and slide it into place. Figure 13. Drip sensor assembly installation 
- Reinstall all EMC shields. Figure 14. Upper EMC shields installation Figure 15. Lower EMC shield installation Figure 15. Lower EMC shield installation 
- Connect any cables that you disconnected from the modules in the rear of the chassis.
- Connect the chassis to power (see n1200 Enclosure Installation and Service Guide).
- Write down new chassis midplane serial number (for example: Y030UN34B063) and UUID (for example: 2E2B686CC6B311E2907C6EAE8B16A49E).
- Update the server firmware to the latest level (see n1200 Enclosure Installation and Service Guide).
- Log in to the web interface (see n1200 Enclosure Installation and Service Guide).
- Go to System Information section, click on the Midplane VPD tab.
- Update the new chassis midplane serial number and UUID onto the fan and power controller (see n1200 Enclosure Installation and Service Guide).
- Close the release handles on the compute nodes in order to seat the nodes in the chassis midplane connectors.
- Restart any compute nodes that you shut down. See the documentation that comes with the compute node for detailed instructions.
- The fan and power controller is powered-on automatically by the IMM2.