Environmental specifications
Summary of the environmental specifications of solution. Depending on the model, some features might not be available, or some specifications might not apply.
Environment quality must be maintained over the lifetime of the system to receive warranty and support on affected components. For water quality requirement, see Lenovo Neptune Direct Water-Cooling Standards.
Up to eight SC777 V4 trays can be installed in an N1380 13U enclosure.
Each SC777 V4 tray contains two GB200-NVL4 boards
| Environment |
|---|
Note The solution is designed for standard data center environment and is recommended for placement in an industrial data center. |
Water requirements — pressure drop
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC777 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.63 | 0.64 | 0.65 | 0.65 |
| 2 | 0.64 | 0.65 | 0.66 | 0.67 |
| 3 | 0.66 | 0.67 | 0.69 | 0.70 |
| 4 | 0.68 | 0.70 | 0.72 | 0.73 |
| 5 | 0.71 | 0.73 | 0.75 | 0.77 |
| 6 | 0.75 | 0.77 | 0.79 | 0.83 |
| 7 | 0.79 | 0.82 | 0.84 | 0.88 |
| 8 | 0.84 | 0.87 | 0.89 | 0.93 |
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC777 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.46 | 0.46 | 0.46 | 0.48 |
| 2 | 0.47 | 0.47 | 0.48 | 0.50 |
| 3 | 0.48 | 0.49 | 0.50 | 0.52 |
| 4 | 0.50 | 0.51 | 0.52 | 0.54 |
| 5 | 0.53 | 0.54 | 0.55 | 0.57 |
| 6 | 0.55 | 0.57 | 0.58 | 0.62 |
| 7 | 0.58 | 0.60 | 0.62 | 0.65 |
| 8 | 0.62 | 0.64 | 0.66 | 0.70 |
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC777 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.29 | 0.29 | 0.30 | 0.31 |
| 2 | 0.30 | 0.30 | 0.31 | 0.32 |
| 3 | 0.31 | 0.32 | 0.32 | 0.34 |
| 4 | 0.32 | 0.33 | 0.34 | 0.35 |
| 5 | 0.34 | 0.35 | 0.35 | 0.37 |
| 6 | 0.36 | 0.37 | 0.38 | 0.39 |
| 7 | 0.38 | 0.39 | 0.40 | 0.42 |
| 8 | 0.40 | 0.41 | 0.43 | 0.45 |
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC777 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.25 | 0.25 | 0.25 | 0.25 |
| 2 | 0.25 | 0.26 | 0.26 | 0.26 |
| 3 | 0.26 | 0.27 | 0.27 | 0.28 |
| 4 | 0.27 | 0.28 | 0.28 | 0.30 |
| 5 | 0.29 | 0.29 | 0.30 | 0.32 |
| 6 | 0.30 | 0.31 | 0.32 | 0.33 |
| 7 | 0.32 | 0.33 | 0.34 | 0.35 |
| 8 | 0.34 | 0.35 | 0.36 | 0.38 |
Water requirements — water flow rates
| Water requirements — water flow rates |
|---|
Attention The water required to initially fill the system side cooling loop must be reasonably clean, bacteria-free water (<100 CFU/ml) such as de-mineralized water, reverse osmosis water, de-ionized water, or distilled water. The water must be filtered with an in-line 50 micron filter (approximately 288 mesh). The water must be treated with anti-biological and anti-corrosion measures. Environment quality must be maintained over the lifetime of the system to receive warranty and support on affecting components. For more information, please see Water flow rates
For example, when an N1380 enclosure is installed with eight SC777 V4 trays and four PCS, and the water temperature is 45°C, the enclosure water flow rate is 69.6 lpm (7.0 lpm*8 plus 3.4 lpm*4) |