Saltar al contenido principal

FQXSPPW0063M : SysBrd voltage fault has transitioned to critical from a less severe state.

SysBrd voltage fault has transitioned to critical from a less severe state.

This message is for the use case when an implementation has detected a Sensor transitioned to critical from less severe.

Severity

Error

Alert Category

Critical - Voltage

Serviceable

Yes

CIM Information

Prefix:PLAT

and ID:0522

SNMP Trap ID

1

Automatically Notify Support

Yes

User Action

Complete the following steps until the problem is solved:

  1. Perform virtual system reseat or A/C power cycle.
  2. If the error persists, remove A/C power and any recently installed components.
  3. If the system successfully powers on, complete the following steps:
    1. Check the Server Proven website (http://www.lenovo.com/us/en/serverproven/index.shtml) to make sure that recently installed components are compatible with the system.
    2. Inspect the previously installed components for physical damage and fix it.
    3. If the system does not successfully power on or if this is not the first occurrence of this problem, go to step 4.
  4. If the problem persists, collect service data log.
  5. Contact Lenovo Support.