Remove the fixed power supply unit

Use this information to remove the fixed power supply unit.

To avoid possible danger, read and follow the following safety information.

S001
shock hazard
DANGER
danger
Electrical current from power, telephone, and communication cables is hazardous.

To avoid a shock hazard:

  • Connect all power cords to a properly wired and grounded electrical outlet/source.
  • Connect any equipment that will be attached to this product to properly wired outlets/sources.
  • When possible, use one hand only to connect or disconnect signal cables.
  • Never turn on any equipment when there is evidence of fire, water, or structural damage.
  • The device might have more than one power cord, to remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S002
disconnect all power
CAUTION
The power-control button on the device and the power switch on the power supply do not turn off the electrical current supplied to the device. The device also might have more than one power cord. To remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S035
shock hazard
CAUTION

Never remove the cover on a power supply or any part that has this label attached. Hazardous voltage, current, and energy levels are present inside any component that has this label attached. There are no serviceable parts inside these components. If you suspect a problem with one of these parts, contact a service technician.

Before you remove the fixed power supply unit, complete the following steps:

  1. Read Safety and Installation Guidelines to ensure that you work safely.

  2. Turn off the server. Disconnect the power cords and all external cables (see Power off the server).

  3. If server is installed in a rack, remove the server from the rack.

  4. Remove the top cover (see Remove the top cover).

  5. Disconnect internal power cable of power supply unit from system board.

To remove the fixed power supply unit, complete the following steps:

Figure 1. Power supply unit removal
Power supply unit removal
  1. Remove the screws on the rear side of the server.
  2. Slide the power supply unit forward until the pins align with the opening of the slots.
  3. Lift the power supply unit out of the server.

If you are instructed to return the component or optional device, follow all packaging instructions, and use any packaging materials for shipping that are supplied to you.