Skip to main content

Removing a hot-swap fan

Use this information to remove a hot-swap fan.

Attention
To ensure proper server operation, replace a failed hot-swap fan within 30 seconds.

To remove a hot-swap-fan, complete the following steps:

  1. Read the safety information that begins on Safety and Guidelines.
  2. Remove the top cover (see Removing the top cover). The LED on the system board near the connector for the failing dual-motor hot-swap fan will be lit.
    Attention
    It is not necessary to disconnect the power when removing the hot-swap fan. To ensure proper system cooling, do not remove the top cover for more than 30 minutes during this procedure.
  3. 1 Pull the fan latch to the left to release the fan from the fan connector and 2 pull the fan out of the fan cage.
    Figure 1. Fan removal
    Fan removal
    Attention
    To ensure proper operation, replace a failed hot-swap fan within 30 seconds.
  4. If you are instructed to return the fan, follow all of the packaging instructions, and use any packaging materials for shipping that are supplied to you.