Skip to main content

02010009 : SMM2 Brd 1.2V: Voltage sensor, warning event was asserted, reading value %V (Threshold %V)

SMM2 Brd 1.2V: Voltage sensor, warning event was asserted, reading value %V (Threshold %V)

Asserted when voltage sensed on 1.2V power rail is lower than lower non-critical threshold.

Severity

Warning

Alert Category

System - SMM2 system event

SNMP Trap ID

33619977

User Action

  1. Virtual reset SMM2 via Web GUI or IPMI command.
  2. If the event persists, ensure all populated compute nodes are completely power off, then reseat SMM2 module. (Service technician only)
  3. If the event persists, ensure all populated compute nodes are completely power off, then replace the SMM2 module. (Service technician only)
  4. If the event persists, please consult with technical service.