Skip to main content

08070795 : PSU 4 EPOW: Power Supply, Monitor was asserted.

PSU 4 EPOW: Power Supply, Monitor was asserted.

The indicated power supply reports an early power off warning owing to its input power reaches undervoltage or overvoltage lockout limit.

Severity

Information

Alert Category

PSU - Power Supply event

SNMP Trap ID

134678421

User Action

  1. Check LED status of indicated power supply as
    • If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated power supply.
    • If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
    • If Fault Indicator (!) is lit on, replace indicated power supply.
  2. If the event persists, please consult with technical service.