Skip to main content

0201090D : SMM2 Brd 12V: Voltage sensor, critical event was asserted, reading value %V (Threshold %V)

SMM2 Brd 12V: Voltage sensor, critical event was asserted, reading value %V (Threshold %V)

Asserted when voltage sensed on 12V power rail is higher than upper critical threshold.

Severity

Error

Alert Category

System - SMM2 system event

SNMP Trap ID

33622285

User Action

  1. Virtual reset SMM2 via Web GUI or IPMI command.
  2. If the event persists, ensure all populated compute nodes are completely power off, then reseat SMM2 module. (Service technician only)
  3. If the event persists, ensure all populated compute nodes are completely power off, then replace the SMM2 module. (Service technician only)
  4. If the event persists, please consult with technical service.