Rear Door Heat eXchanger for 48U Rack
See this topic to learn about parts of ThinkSystem Rear Door Heat eXchanger for 48U Rack.
1 Rear Door Heat eXchanger assembly | 7 Lift handles |
2 Air-purging valve | 8 Lift handle |
3 Air-purging tool | 9 Serial number |
4 Door latch | 10 Lift handle |
5 Latch plate | 11 Lower air baffle |
6 Hinge kit | 12 Upper air baffle |
For setup and installation, see Set up Rear Door Heat eXchanger for 48U Rack.
Specifications
Dimension |
|
Weight | Empty: 49 kg / 103.6 lbs |
Air movement | Provided by servers and other devices in the rack |
Air temperature drop | With high-heat-load devices, up to 25°C (45°F) between the air exiting the rack devices and the air exiting the heat exchanger. |
Water |
|
Heat exchanger performance
The following figure illustrates the diagram of rack air flow and heat exchanger water flow.
Expected performance of the heat exchanger is illustrated in the following figures for 25°C (77°F) rack entering air temperature and typical rack air flow of 3840SCFM and 4800SCFM. By selecting the correct rack power, water inlet temperature, you can achieve the water flow rate (lpm) for 100% heat removal. Water flow rate (lpm) for 100% heat removal indicates that an amount of heat equivalent to that generated by the devices has been removed by the heat exchanger and the average air temperature leaving the heat exchanger is identical to that entering the rack (25°C /77°F in this example).
Heat removal as function of water inlet temperature and water flow rate for the given rack entering air temperature and air flow rate.
Heat removal as function of water inlet temperature and water flow rate for the given rack entering air temperature and air flow rate.