18040179 : DripSensor 1 Out: Chassis, Predictive Failure asserted was asserted.
DripSensor 1 Out: Chassis, Predictive Failure asserted was asserted.
The indicated drip tray detects the leakage from water loop.
Severity
Warning
Alert Category
System - SMM2 system event
SNMP Trap ID
402915705
User Action
- Check the indicated drip tray for water leakage.
- Clean the indicated drip tray.
- Ensure the indicated drip tray is correctly installed.
- If the event persists, please consult with technical service.