21070148 : Node 9 Pwr Perm: Slot Or Connector, transition to Non-Critical from OK was asserted.
Node 9 Pwr Perm: Slot Or Connector, transition to Non-Critical from OK was asserted.
The indicated compute node hasn't acquired power permission to into ready state.
Severity
Warning
Alert Category
Node - Node event
SNMP Trap ID
554107208
User Action
- Please check the enclosure event refer to following section
- For DW612 enclosure
- If the Shared IO mode is enabled, the auxiliary node will acquire power permisson once the primary node is power on.
- For DA240 enclosure
- Ensure all fan modules are well installed and have no fault event.
- For DW612 enclosure
- If the event persists, reseat the indicated compute node if the node is under power fault condition. (Service technician only)
- If the event persists, reset the BMC on indicated compute node.
- If the event persists, ensure the indicated compute node is completely power off and then reseat it. (Service technician only)
- If the event persists, replace the indicated compute node. (Service technician only)
- If the event persists, please consult with technical service.
Give documentation feedback