FPC events
The following events can be viewed from the FPC web interface.
For each event code, the following fields are displayed:
- Event identifier
- An identifier that uniquely identifies an event.
- Event description
- The logged message string that appears for an event.
- Explanation
- Provides additional information to explain why the event occurred.
- Severity
- An indication of the level of concern for the condition. The severity is abbreviated in the event log to the first character. The following severities can be displayed:
Informational/ Normal. The event was recorded for audit purposes, usually a user action or a change of states that is normal behavior.
Warning. The event is not as severe as an error, but if possible, the condition should be corrected before it becomes an error. It might also be a condition that requires additional monitoring or maintenance.
Critical . The event is a failure or critical condition that impairs service or an expected function.
- Serviceable
- Specifies whether user action is required to correct the problem.
- User response
- Indicates what actions you should perform to solve the event. Perform the steps listed in this section in the order shown until the problem is solved. If you cannot solve the problem after performing all steps, contact Lenovo Support.
- 02 : EvtLogDisabled: Event Logging Disabled sensor, Log Area Reset/Cleared was asserted.
EvtLogDisabled: Event Logging Disabled sensor, Log Area Reset/Cleared was asserted. - 03 : EvtLogDisabled: Event Logging Disabled sensor, system event log full was asserted
EvtLogDisabled: Event Logging Disabled sensor, system event log full was asserted - 04 : EvtLogDisabled: Event Logging Disabled sensor, system event log almost full was asserted
EvtLogDisabled: Event Logging Disabled sensor, system event log almost full was asserted - 10 : FAN_Tach_1A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_1A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 11 : FAN_Tach_1B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_1B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 12 : FAN_Tach_2A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_2A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 13 : FAN_Tach_2B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_2B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 14 : FAN_Tach_3A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_3A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 15 : FAN_Tach_3B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_3B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 16 : FAN_Tach_4A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_4A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 17 : FAN_Tach_4B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_4B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 18 : FAN_Tach_5A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_5A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 19 : FAN_Tach_5B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_5B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 1A : FAN_Tach_6A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_6A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 1B : FAN_Tach_6B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_6B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 1C : FAN_Tach_7A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_7A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 1D : FAN_Tach_7B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_7B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 1E : FAN_Tach_8A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_8A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 1F : FAN_Tach_8B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_8B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 20 : FAN_Tach_9A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_9A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 21 : FAN_Tach_9B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_9B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 22 : FAN_Tach_10A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_10A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 23 : FAN_Tach_10B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM)
FAN_Tach_10B: Fan sensor, failure event was asserted, reading value : %RPM (Threshold : 1472RPM) - 30 : 12V_Sense
12V_Sense - 31 : 3V3_Sense
3V3_Sense - 32 : 5V_Sense
5V_Sense - 33 : VBAT_Sense
VBAT_Sense - 40 : PS1_FANFault
PS1_FANFault - 41 : PS1_Thermal_Fault
PS1_Thermal_Fault - 42 : PS1_12V_OV_Fault
PS1_12V_OV_Fault - 43 : PS1_12V_UV_Fault
PS1_12V_UV_Fault - 44 : PS1_12V_AUX_Fault
PS1_12V_AUX_Fault - 45 : PS1_EPOW_Assert
PS1_EPOW_Assert - 46 : PS1_Throttle_Assert
PS1_Throttle_Assert - 47 : PS1_AC_Lo_Line
PS1_AC_Lo_Line - 48 : PS1_OT_Warning
PS1_OT_Warning - 49 : PS1_No_Present
PS1_No_Present - 50 : PS2_FANFault
PS2_FANFault - 51 : PS2_Thermal_Fault
PS2_Thermal_Fault - 52 : PS2_12V_OV_Fault
PS2_12V_OV_Fault - 53 : PS2_12V_UV_Fault
PS2_12V_UV_Fault - 54 : PS2_12V_AUX_Fault
PS2_12V_AUX_Fault - 55 : PS2_EPOW_Assert
PS2_EPOW_Assert - 56 : PS2_Throttle_Assert
PS2_Throttle_Assert - 57 : PS2_AC_Lo_Line
PS2_AC_Lo_Line - 58 : PS2_OT_Warning
PS2_OT_Warning - 59 : PS2_No_Present
PS2_No_Present - 60 : PS3_FANFault
PS3_FANFault - 61 : PS3_Thermal_Fault
PS3_Thermal_Fault - 62 : PS3_12V_OV_Fault
PS3_12V_OV_Fault - 63 : PS3_12V_UV_Fault
PS3_12V_UV_Fault - 64 : PS3_12V_AUX_Fault
PS3_12V_AUX_Fault - 65 : PS3_EPOW_Assert
PS3_EPOW_Assert - 66 : PS3_Throttle_Assert
PS3_Throttle_Assert - 67 : PS3_AC_Lo_Line
PS3_AC_Lo_Line - 68 : PS3_OT_Warning
PS3_OT_Warning - 69 : PS3_No_Present
PS3_No_Present - 70 : PS4_FANFault
PS4_FANFault - 71 : PS4_Thermal_Fault
PS4_Thermal_Fault - 72 : PS4_12V_OV_Fault
PS4_12V_OV_Fault - 73 : PS4_12V_UV_Fault
PS4_12V_UV_Fault - 74 : PS4_12V_AUX_Fault
PS4_12V_AUX_Fault - 75 : PS4_EPOW_Assert
PS4_EPOW_Assert - 76 : PS4_Throttle_Assert
PS4_Throttle_Assert - 77 : PS4_AC_Lo_Line
PS4_AC_Lo_Line - 78 : PS4_OT_Warning
PS4_OT_Warning - 79 : PS4_No_Present
PS4_No_Present - 80 : PS5_FANFault
PS5_FANFault - 81 : PS5_Thermal_Fault
PS5_Thermal_Fault - 82 : PS5_12V_OV_Fault
PS5_12V_OV_Fault - 83 : PS5_12V_UV_Fault
PS5_12V_UV_Fault - 84 : PS5_12V_AUX_Fault
PS5_12V_AUX_Fault - 85 : PS5_EPOW_Assert
PS5_EPOW_Assert - 86 : PS5_Throttle_Assert
PS5_Throttle_Assert - 87 : PS5_AC_Lo_Line
PS5_AC_Lo_Line - 88 : PS5_OT_Warning
PS5_OT_Warning - 89 : PS5_No_Present
PS5_No_Present - 90 : PS6_FANFault
PS6_FANFault - 91 : PS6_Thermal_Fault
PS6_Thermal_Fault - 92 : PS6_12V_OV_Fault
PS6_12V_OV_Fault - 93 : PS6_12V_UV_Fault
PS6_12V_UV_Fault - 94 : PS6_12V_AUX_Fault
PS6_12V_AUX_Fault - 95 : PS6_EPOW_Assert
PS6_EPOW_Assert - 96 : PS6_Throttle_Assert
PS6_Throttle_Assert - 97 : PS6_AC_Lo_Line
PS6_AC_Lo_Line - 98 : PS6_OT_Warning
PS6_OT_Warning - 99 : PS6_No_Present
PS6_No_Present - A0 : Node01_BMC_Fault
Node01_BMC_Fault - A1 : Node02_BMC_Fault
Node02_BMC_Fault - A2 : Node03_BMC_Fault
Node03_BMC_Fault - A3 : Node04_BMC_Fault
Node04_BMC_Fault - A4 : Node05_BMC_Fault
Node05_BMC_Fault - A5 : Node06_BMC_Fault
Node06_BMC_Fault - A6 : Node07_BMC_Fault
Node07_BMC_Fault - A7 : Node08_BMC_Fault
Node08_BMC_Fault - A8 : Node09_BMC_Fault
Node09_BMC_Fault - A9 : Node10_BMC_Fault
Node10_BMC_Fault - AA : Node11_BMC_Fault
Node11_BMC_Fault - AB : Node12_BMC_Fault
Node12_BMC_Fault - AC : PSU_Unbalance
PSU_Unbalance - AD : PSU_Missmatch
PSU_Missmatch - AE : PSU_Not_Support
PSU_Not_Support - AF : PSU_Policy_Loses
PSU_Policy_Loses - B2 : FAN01_No_Present
FAN01_No_Present - B3 : FAN02_No_Present
FAN02_No_Present - B4 : FAN03_No_Present
FAN03_No_Present - B5 : FAN04_No_Present
FAN04_No_Present - B6 : FAN05_No_Present
FAN05_No_Present - B7 : FAN06_No_Present
FAN06_No_Present - B8 : FAN07_No_Present
FAN07_No_Present - B9 : FAN08_No_Present
FAN08_No_Present - BA : FAN09_No_Present
FAN09_No_Present - BB : FAN10_No_Present
FAN10_No_Present - BC : Zone %_FAN_FFS
Zone %_FAN_FFS - BD : Zone %_PSU_FFS
Zone %_PSU_FFS - BE : Leak_Snsr1_FAULT
Leak_Snsr1_FAULT - BF : Leak_Snsr2_FAULT
Leak_Snsr2_FAULT - C0 : First_Perm_Fail
First_Perm_Fail - C1 : Failsafe_No_Perm
Failsafe_No_Perm - C2 : Node_Reseat_User
Node_Reseat_User - C3 : Node_Reset_User
Node_Reset_User - C4 : Node_No_Present
Node_No_Present - C5 : Node_DC_OFF
Node_DC_OFF - C6 : Second_Perm_Fail
Second_Perm_Fail - C7 : Restore_Cap_Fail
Restore_Cap_Fail - C8 : EPOW_OUT
EPOW_OUT - C9 : Throttle_OUT
Throttle_OUT - CA : Chassis_Cap_Low
Chassis_Cap_Low - CB : Node_Cap_Low
Node_Cap_Low - CC : USB Key Missing
USB Key Missing - CD : Node_Reseat_FPC
Node_Reseat_FPC - CE : Hi_PCI_NOACSTIC
Hi_PCI_NOACSTIC - CF : Node %_Hi_PCI_Card
Node %_Hi_PCI_Card - D0 : Chassis_No_PermF1
Chassis_No_PermF1 - D1 : Nodes_Power_2Big
Nodes_Power_2Big - D2 : Throttle_OUT_FPC
Throttle_OUT_FPC - D3 : FPC_REBOOT
FPC_REBOOT - D4 : USER_RST_DEFAULT
USER_RST_DEFAULT - D5 : FPC_POWER_ON
FPC_POWER_ON - D6 : PS_0_OUTPUT_FAIL
PS_0_OUTPUT_FAIL - E0 : LeakSnr1_Missing
LeakSnr1_Missing - E1 : LeakSnr2_Missing
LeakSnr2_Missing