Skip to main content

Remove the manifold

Use this information to remove the manifold.

CAUTION

The water might cause irritation to the skin and eyes. Avoid direct contact with the lubricant.

S002
disconnect all power
CAUTION
The power-control button on the device and the power switch on the power supply do not turn off the electrical current supplied to the device. The device also might have more than one power cord. To remove all electrical current from the device, ensure that all power cords are disconnected from the power source.
S038
Use eye protection
CAUTION
Eye protection should be worn for this procedure.














Attention
Ensure proper handling procedures are followed when working with any chemically treated water used in the compute rack cooling system. Ensure that material safety data sheets (MSDS) and safety information are provided by the water chemical treatment supplier and that proper personal protective equipment (PPE) is available as recommended by the water chemical treatment supplier. Protective gloves and eyewear may be recommended as a precaution.

Before you remove the manifold:

  1. Read the Installation Guidelines to ensure that you work safely.

Complete the following steps to remove the manifold.

  1. Slide all DWC trays in the entire rack out of the enclosure about 4-inch or 100 mm (see Remove a DWC tray from the enclosure).
  2. At the front of the rack, close both Eaton ball valves.
    Figure 1. Eaton ball valves closed
    Eaton ball valves closed
    Table 1. Eaton ball valves
    1 Rack supply2 Rack return
  3. Remove EMC shields on both sides of the top enclosure.
    Figure 2. EMC shields removal
    EMC shields removal
    Figure 3. EMC shields removal
    EMC shields removal
  4. Remove the red quick connect plug covers from the tops of each manifold.
    Figure 4. Quick connect plug covers removal
    Quick connect plug covers removal
  5. Place the open blue hose end of the drain hose (tool left at customer site) into a bucket. Make sure that the lever on the drain hose valve is closed (lever is pointed away from the hose).
    Figure 5. Water draining
    Water draining
  6. Connect the Quick connect socket from the drain hose tool to the top of the return side manifold (position middle of the rack).
    Figure 6. Quick connect socket from the drain hose tool to the top of the return side manifold connection
    Quick connect socket from the drain hose tool to the top of the return side manifold connection
  7. Once the quick connect is attached, slowly open the hose valve and allow water to drain until water stops flowing (approximately 1 minute).
    Figure 7. Water draining
    Water draining
  8. Move to the top position of the other manifold (position closest to the rack side wall). Leave the hose connected to the top of the manifold until water stops flowing. Disconnect quick connect from top of manifold.
    Figure 8. Quick connect socket from the drain hose tool to the top of the supply side manifold connection
    Quick connect socket from the drain hose tool to the top of the supply side manifold connection
  9. Continue to each enclosure from the top enclosure to the bottom enclosure by reaching into each enclosure Location C and Location D quick connects and allow for a steady stream of water to drain. Repeat drain process until all positions in the entire rack have been drained.
  10. Re-attach the hose which should be put onto the manifold that has the section to be replaced to the top of the manifold before moving back around to the front of the rack.
  11. At this point, the manifold should be properly drained to allow for service. Since there still can be some water left in the manifold, prepare work area with absorbent cloths to collect any water that may drain out.
  12. Determine which manifold needs to be replaced.
  13. Move to the rear of the rack. Remove manifold retention bracket that is retaining the manifold (top enclosure position only).
    Figure 9. Retention bracket removal
    Retention bracket removal
  14. Push the latch up upwards and slide the drip sensor assembly backwards, then; lift the drip sensor assembly up to clear sensor post and pull it out of the enclosure.
    Figure 10. Drip sensor assembly removal
    Drip sensor assembly removal
    Figure 11. Drip sensor assembly
    Drip sensor assembly
    Table 2. Drip sensor assembly
    1 Connector2 Latch
  15. Remove FPC card module and FPC card module support bracket if portion of left manifold is being replaced. If it is the right side manifold, remove blank filler.
    Figure 12. FPC card module removal
    FPC card module removal
    Figure 13. Support bracket removal
    Support bracket removal
  16. Unscrew four screws (using the screwdriver contained in the manifold repair kit) to loosen the manifold bracket from the enclosure.
    Figure 14. Manifold screw locations
    Manifold screw locations
    Table 3. Manifold screw locations
    1 Screws2 Manifold
  17. Repeat steps 14-17 for all manifold sections until you can freely access the entire manifold to be replaced.
  18. Remove the entire manifold and lay it on the ground for the next steps.
  19. Place a pan under the section of the manifold to be removed.
    Figure 15. Manifold disassemble
    Manifold disassemble
    Table 4. Manifold disassemble
    1 41mm wrench
  20. Disconnect manifold section to be replaced from the rest of the manifold by disconnecting the couplings. Use 41mm wrench supplied with replacement manifold section kit.

If you are instructed to return the component or optional device, follow all packaging instructions, and use any packaging materials for shipping that are supplied to you.