Thermal rules
This topic lists the thermal rules for the server to comply with ASHRAE class A2, A3, or A4 specifications.
ASHARE class A2 environment
The following table lists the ambient temperature requirement for the server depending on the hardware configuration.
Model | Default TDP | Configuration | Max. Ambient Temp. |
All models |
| 35°C | |
| 30°C | ||
4 x 2.5'' models | 280 W |
| 35°C |
2 Tesla T4/A2 GPUs | 35°C | ||
8 x 2.5''/4 x 3.5'' models | 120 W / 155 W | 2 x 2.5'' SSD | 35°C |
180W / 190 W / 200 W | 3 Tesla T4/A2 GPUs | 35°C | |
2 x 2.5'' SSD | 30°C | ||
225 W /240 W |
| 35°C | |
280 W |
| 30°C | |
10 x 2.5'' models | 120 W / 155 W |
| 35°C |
180W / 190 W / 200 W |
| 35°C | |
3 Tesla T4/A2 GPUs | 30°C | ||
225 W /240 W |
| 35°C | |
280 W |
| 30°C |
ASHARE class A3/A4 environment
To comply with ASHARE class A3/A4 specifications, the server must NOT be configured with below components:
CPU (TDP ≥ 170W)
3DS RDIMMs
GPUs
Mellanox ConnectX-6 100 GbE/200GbE with AOC
NVIDIA ConnectX-7 200 GbE/400GbE with AOC
Xilinx Alveo U25 FPGA
Broadcom 57454 OCP 3.0
NVMe AIC switches
2 x 7mm SSDs
2 x 2.5'' SSDs