Environmental specifications
Summary of the environmental specifications of server. Depending on the model, some features might not be available, or some specifications might not apply.
Environment quality must be maintained over the lifetime of the system to receive warranty and support on affecting components. For water quality requirement, see Lenovo Neptune Direct Water-Cooling Standards.
Acoustical noise emissions
Acoustical noise emissions | ||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
The server has the following acoustic noise emissions declaration.
Note
|
Environment
Environment |
---|
ThinkSystem SR650 V4 complies with ASHRAE Class A2 specifications with most configurations, and depending on the hardware configuration, also complies with ASHRAE Class A3 and Class A4 specifications. System performance may be impacted when the operating temperature is outside ASHRAE A2 specification. Depending on the hardware configuration, SR650 V4 server also complies with ASHRAE Class H1 specification. System performance may be impacted when the operating temperature is outside ASHRAE H1 specification. For detailed thermal information, see Thermal rules. Note When the ambient temperature is greater than the supported max temperature (ASHRAE A4 45°C), the server will shut down. The server will not power on again until the ambient temperature falls within the supported temperature range. The restrictions to ASHRAE support are as follows (cooling by air):
The restrictions to ASHRAE support are as follows (cooling by Processor Neptune Core Module):
The restrictions to ASHRAE support are as follows (cooling by Compute Complex Neptune Core Module):
|
Water requirements
Water requirements | ||||||||
---|---|---|---|---|---|---|---|---|
ThinkSystem SR650 V4 is supported in the following environment:
Attention The water required to initially fill the system side cooling loop must be reasonably clean, bacteria-free water (<100 CFU/ml) such as de-mineralized water, reverse osmosis water, de-ionized water, or distilled water. The water must be filtered with an in-line 50 micron filter (approximately 288 mesh). The water must be treated with anti-biological and anti-corrosion measures. Environment quality must be maintained over the lifetime of the system to receive warranty and support on affecting components. For more information, see |