Summary of the environmental specifications of server. Depending on the model, some features might not be available, or some specifications might not apply.
Environment |
---|
ThinkSystem SR680a V3 complies with ASHRAE Class A2 specifications with certain thermal restrictions. System performance may be impacted when operating temperature is out of permitted conditions. - Air temperature:
- Operating
- ASHARE Class A2: 10°C to 35°C (50°F to 95°F); the maximum ambient temperature decreases by 1°C for every 300 m (984 ft) increase in altitude above 900 m (2,953 ft).
- Server off: 5°C to 45°C (41°F to 113°F)
- Shipment/storage: -20°C to 60°C (-4°F to 140°F)
- Maximum altitude: 3,050 m (10,000 ft)
- Relative Humidity (non-condensing):
- Operating
- ASHRAE Class A2: 8% to 80%; maximum dew point: 21°C (70°F)
- Shipment/storage: 8% to 90%
- Particulate contamination
Airborne particulates and reactive gases acting alone or in combination with other environmental factors such as humidity or temperature might pose a risk to the server. For information about the limits for particulates and gases, see Particulate contamination.
The server is designed for standard data center environment and recommended to be placed in industrial data center. |