Environmental specifications

Summary of the environmental specifications of server. Depending on the model, some features might not be available, or some specifications might not apply.

Acoustical noise emissions

The server has the following acoustic noise emissions declaration:

Table 1. Acoustic noise emissions declaration

Acoustic performance @ 25°C ambient

Working modeConfiguration
TypicalMax.

Declared mean A-weighted sound power level, LWA,m (B)

Statistical adder for verification, Kv (B) = 0.4

Idle6.86.8
Operating mode 17.27.9
Operating mode 27.98.5

Declared mean A-weighted emission sound pressure level, LpA,m (dB)

Bystander position

Idle5353
Operating mode 15866
Operating mode 26672
Note
  • These sound levels were measured in controlled acoustical environments according to procedures specified by ISO7779 and are reported in accordance with ISO 9296.

  • Idle mode is the steady state in which the server is powered on but not operating any intended function. Operating mode 1 is 50% CPU TDP. Operating mode 2 is 100% CPU TDP.

  • The declared acoustic sound levels are based on the following configurations, which may change depending on configuration or conditions.
    • Typical: 4 x 270W CPUs, 32 x 64 GB RDIMMs, 24 x 2.5" SAS HDDs, 1 x RAID 545-8i, 1 x Intel E610-T4 10GBASE-T 4-port OCP, 4 x 2000W PSUs

    • Max.: 4 x 350W CPUs, 64 x 64 GB RDIMMs, 48 x 2.5" SAS HDDs, 3 x RAID 940-16i, 2 x Intel E610-T4 10GBASE-T 4-port OCP, 4 x 3200W PSUs

  • Government regulations (such as those prescribed by OSHA or European Community Directives) may govern noise level exposure in the workplace and may apply to you and your server installation. The actual sound pressure levels in your installation depend upon a variety of factors, including the number of racks in the installation; the size, materials, and configuration of the room; the noise levels from other equipment; the room ambient temperature, and employee's location in relation to the equipment. Further, compliance with such government regulations depends on a variety of additional factors, including the duration of employees' exposure and whether employees wear hearing protection. Lenovo recommends that you consult with qualified experts in this field to determine whether you are in compliance with the applicable regulations.

Ambient temperature management

Manage the ambient temperature for your server depending on the specific hardware components installed.

Note
The tables below show the temperature limits for servers without a liquid-cooling module (Processor Neptune® Core Module). When the liquid-cooling module is installed, the CPU supports temperatures up to 45°C regardless of the fan type or number of drives. However, other components like the GPU and NIC adapters still need to follow the same temperature limits as air-cooled systems, which are listed below.

Server models with 2.5-inch drive bays

System fanMax. ambient temp.1CPU TDPDIMM capacity (per module)Max. drive qty.Rear M.2 drivesGPU adapterNIC adapter
Standard fans40°C/45°C<= 165W<= 32 GB48NoneNoneNone
Standard fans35°C<=210W<= 32 GB48NoneNoneNone
Standard fans30°C<=270W<= 64 GB2482NoneNone
Standard fans25°C<=270W<= 64 GB2482NoneSee note3
Performance fans40°C/45°C<=270W<= 32 GB48NoneNoneNone
Performance fans35°C<=350W<= 64 GB48NoneNoneSee note3,4
Performance fans30°C<=350W<= 128 GB482See note5See note3,4,5
Performance fans25°C<=350W<= 128 GB482See note5See note3,4,5
Ultra fans40°C/45°C<=270W<= 64 GB48NoneNoneNone
Ultra fans35°C<=350W<= 128 GB482NoneSee note3,4
Ultra fans30°C<=350W<= 128 GB482See note6See note3,4,5
Ultra fans25°C<=350W<= 256 GB7482See note6See note3,4,5
Note
  1. The server's performance may be impacted if operated under 40°C/45°C.

  2. The 64 GB RDIMMs are supported in servers with only 24 x 2.5-inch drives.

  3. NIC adapters without active optic cables (AOC) are supported.

  4. NIC adapters with AOC cables are supported. When the CPU TDP is 270W or lower, the ambient temperature can be up to 35°C.

  5. The Broadcom BCM57608 2x200G OCP Ethernet adapter is supported in servers with only 24 x 2.5-inch drives.

  6. A maximum of four double-wide (DW) GPU adapters or eight single-wide (SW) GPU adapters are supported. When DW GPU adapters are installed, the 2U performance heat sinks must be used for processor 1 and processor 2.

  7. The 256 GB RDIMMs are supported in servers with only 24 x 2.5-inch drives.

Server models with E3.S bays

System fanMax. ambient temp.CPU TDPDIMM capacity (per module)Max. drive qty.1Rear M.2 drivesGPU adapterNIC adapter
Ultra fans35°C<=350W<= 128 GB32 + 24NoneNoneSee note2,3
Ultra fans30°C<=350W<= 128 GB32 + 242See note4See note2,3
Ultra fans25°C<=350W<= 128 GB32 + 242See note4See note2,3
Note
  1. Supports up to 32 x E3.S 1T drives and 24 x 2.5-inch drives.

  2. NIC adapters without active optic cables (AOC) are supported.

  3. NIC adapters with AOC cables are supported. When the CPU TDP is 270W or lower, the ambient temperature can be up to 35°C.

  4. A maximum of four double-wide (DW) GPU adapters or eight single-wide (SW) GPU adapters are supported. When DW GPU adapters are installed, the 2U performance heat sinks must be used for processor 1 and processor 2.

Environment

Environment

ThinkSystem SR860 V4 complies with ASHRAE Class A2 specifications under most hardware configurations, and depending on specific hardware configuration, it may also comply with ASHRAE Class A3, Class A4, or Class H1 specifications. Refer to Ambient temperature management for information about temperature requirement for specific hardware. The server's performance may be impacted if operated outside the specified ASHRAE temperature classes it complies with.

Note
The server is designed for standard data center environment and recommended to be placed in industrial data center.
  • Air temperature:
    • Operating
      • ASHRAE Class H1: 5°C to 25°C (41°F to 77°F); the maximum ambient temperature decreases by 1°C for every 500 m (1640 ft) increase in altitude above 900 m (2,953 ft).
      • ASHRAE Class A2: 10°C to 35°C (50°F to 95°F); the maximum ambient temperature decreases by 1°C for every 300 m (984 ft) increase in altitude above 900 m (2,953 ft).
      • ASHRAE Class A3: 5°C to 40°C (41°F to 104°F); the maximum ambient temperature decreases by 1°C for every 175 m (574 ft) increase in altitude above 900 m (2,953 ft).
      • ASHRAE Class A4: 5°C to 45°C (41°F to 113°F); the maximum ambient temperature decreases by 1°C for every 125 m (410 ft) increase in altitude above 900 m (2,953 ft).
    • Server off: 5°C to 45°C (41°F to 113°F)
    • Shipment/storage: -40°C to 60°C (-40°F to 140°F)
  • Maximum altitude: 3,050 m (10,000 ft)
  • Relative Humidity (non-condensing):
    • Operating
      • ASHRAE Class H1: 8% to 80%; maximum dew point: 17°C (62.6°F)
      • ASHRAE Class A2: 8% to 80%; maximum dew point: 21°C (70°F)
      • ASHRAE Class A3: 8% to 85%; maximum dew point: 24°C (75°F)
      • ASHRAE Class A4: 8% to 90%; maximum dew point: 24°C (75°F)
    • Shipment/storage: 8% to 90%
  • Particulate contamination
    Attention
    Airborne particulates and reactive gases acting alone or in combination with other environmental factors such as humidity or temperature might pose a risk to the server. For information about the limits for particulates and gases, see Particulate contamination.

Water requirements

Water requirements
ThinkSystem SR860 V4 is supported in the following environment:
  • Maximum pressure: 3 bars

  • Water inlet temperature and flow rates:
    • For servers with Processor Neptune® Core Module, the water inlet temperature and water flow rate can be as follows:
      Water inlet temperatureWater flow rate
      50°C (122°F)1.5 liters per minute (lpm) per server
      45°C (113°F)1 liter per minute (lpm) per server
      40°C (104°F) or lower0.5 liters per minute (lpm) per server
Attention
The water required to initially fill the system side cooling loop must be reasonably clean, bacteria-free water (<100 CFU/ml) such as de-mineralized water, reverse osmosis water, de-ionized water, or distilled water. The water must be filtered with an in-line 50 micron filter (approximately 288 mesh). The water must be treated with anti-biological and anti-corrosion measures. Environment quality must be maintained over the lifetime of the system to receive warranty and support on affecting components. For more information, see Lenovo Neptune Direct Water-Cooling Standards.