Node bays (on front): The chassis has fourteen node bays that support any of the following configurations: - Fourteen 1-bay compute nodes
- Seven 2-bay compute nodes (with the shelves removed from the chassis)
The chassis can also support a combination of 1-bay and 2-bay compute nodes. - A 1-bay compute node occupies one node bay in the chassis.
- A 2-bay compute node occupies two adjacent node bays (horizontally) in the chassis and requires the chassis shelf to be removed prior to installation.
| Cooling: Supports up to 10 variable-speed, hot-swap fan modules: - Two 40 mm fan modules
- Up to eight 80 mm fan modules
Management modules:- Two hot-swap Chassis Management Modules
I/O modules: Supports up to four scalable switch modules with each providing a 4-lane physical interconnect. |
Module bays (on rear):- Two hot-swap Chassis Management Module bays
- Six hot-swap power-supply bays
- Ten hot-swap fan bays
- Four hot-swap I/O bays
- Two hot-swap fan logic bays
| Size (11U):- Height: 483 mm (19.02 in.)
- Depth: 854 mm (33.62 in.)
- Width: 447 mm (17.6 in.)
- Weight:
- Fully configured (stand-alone): approximately 229.16 kg (505.2 lb) 6
- Fully configured (in the rack): approximately 234.28 kg (516.5 lb) 6
- Empty chassis with shelves: approximately 70.44 kg (155.3 lb)
- Empty chassis without shelves: approximately 48.94 kg (107.9 lb)
|
Upgradeable microcode: Microcode is upgradeable when fixes or features are added. - Chassis Management Module firmware
- I/O module firmware
- Compute node firmware
| Approximate heat output: - Minimum configuration: 1365 Btu per hour (400 watts)
- Maximum configuration: 44,017 Btu per hour (12,900 watts)
Declared sound power level: Chassis airflow: Full chassis configuration with all nodes, I/O modules, power supplies, and fan modules installed. - Minimum - 270 CFM
- Maximum - 1,020 CFM
|
Security features:- Login password for remote connection
- Secure Sockets Layer (SSL) security for remote management access
- Lightweight Directory Access Protocol (LDAP)
- Trusted and signed firmware
Predictive Failure Analysis (PFA) alerts:- Power supplies
- Node dependent features
Electrical input with dc supplies:- Rated voltage -48 to -60 V dc
- Maximum steady state current not more than 70 A
- Requires a UL listed circuit breaker that can supply up to 90 A for a minimum of 20 ms
Electrical input with ac supplies:- Rated voltage and frequency 200 - 240 V ac single phase at 47-63 Hz
- Inrush current (chassis maximum) 40 A
- Leakage current (chassis maximum) 580 uA
- Branch circuit breaker 20 A maximum
Power supplies:- Minimum: Two hot-swap power supplies
- Maximum: Six hot-swap power supplies
- 2500 Watt, -48 to -60 V dc power supplies with 2 position power connector (NEBS level 3)
- Optional 2500 Watt, 200 - 240 V ac power supplies with IEC 60320 type C20 line cord connector (ASHRAE Class A3)
| Environment: Flex System Carrier-Grade chassis equipped with -48 V dc power supplies are NEBS level 3 certified. - Operating, low altitude:
- Relative humidity 5% - 85% 1
- Temperature 5°C to 45°C (41°F – 113°F) 2
- Maximum altitude 1829 m (6k ft)
- Maximum rate of temperature change 30°C/hr (80°F/hr) 3
- Operating, high altitude (includes fan failure):
- Relative humidity 5% - 85% 1
- Temperature 5°C to 45°C (41°F - 113°F) 2
- Altitude range 1829-3960 m (6k-13k ft)
- Maximum rate of temperature change 30°C/hr (80°F/hr ) 3
- Operating, short-term excursions (room HVAC failure): 5
- Relative humidity 5% - 93% 1
- Temperature -5°C to 55°C (41°F - 131°F) 2
- Maximum altitude 1829 m (6k ft)
- Non-operating, storage: 4
- Relative humidity 5% - 80% 1
- Temperature 1°C to 70°C (33.8°F - 158°F)
- Altitude 3050 m (10,006 ft)
- Non-operating, shipment: 4
- Relative humidity 5% - 100% 1
- Temperature -40°C to 70°C (-40°F - 158°F)
- Altitude 10,700 m (35,105 ft)
|
- Water to air ratio must never exceed 0.026 kg H20/ kg dry air.
- Derate maximum allowable temperature 1°C/213 m above 1829 m. Also note that this maximum temperature is for a self-standing system, not located in a rack. If in a rack, deduct 5°C.
- 30°C/hr for data centers employing disk drives, tape drives are not used.
- The equipment acclimation period is 1 hour per 30°C of temperature change from the shipping/storage environment to the operating environment.
- One excursion is defined at no more than four days (96 hrs), all excursions per year should not exceed 15 days (360 hrs).
- The fully configured chassis weight is based on all nodes and I/O modules being at their maximum design limit.
|