SC750 V4 installed – Environmental specifications
Summary of the environmental specifications for N1380 enclosure installed with SC750 V4 trays. Depending on the model, some features might not be available, or some specifications might not apply.
Environment quality must be maintain over the lifetime of the system to receive warranty and support on affecting components. For water quality requirement, see Lenovo Neptune Direct Water-Cooling Standards.
Up to eight SC750 V4 trays can be installed in an N1380 13U enclosure.
Each SC750 V4 tray contains two compute nodes, node A and node B. Node A is the bottom node and node B is the top node when viewing the tray from the front of the N1380 enclosure.
Access one set of monitor (VGA port) and keyboard/mouse (USB port) peripheral per N1380 enclosure at a time is recommended per radiated emission compliance.
Environment requirements for N1380 enclosure installed with SC750 V4 trays
| Environment |
|---|
Note The solution is designed for standard data center environment and recommended to be placed in industrial data center. |
Water requirements — pressure drop
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC750 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.39 | 0.38 | 0.41 | 0.42 |
| 2 | 0.35 | 0.40 | 0.41 | 0.42 |
| 3 | 0.39 | 0.40 | 0.42 | 0.43 |
| 4 | 0.40 | 0.41 | 0.42 | 0.44 |
| 5 | 0.41 | 0.42 | 0.43 | 0.45 |
| 6 | 0.41 | 0.43 | 0.44 | 0.46 |
| 7 | 0.43 | 0.44 | 0.46 | 0.47 |
| 8 | 0.44 | 0.45 | 0.47 | 0.49 |
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC750 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.33 | 0.33 | 0.34 | 0.34 |
| 2 | 0.33 | 0.34 | 0.34 | 0.35 |
| 3 | 0.34 | 0.34 | 0.35 | 0.37 |
| 4 | 0.35 | 0.35 | 0.36 | 0.37 |
| 5 | 0.35 | 0.36 | 0.37 | 0.38 |
| 6 | 0.36 | 0.37 | 0.38 | 0.39 |
| 7 | 0.37 | 0.38 | 0.39 | 0.40 |
| 8 | 0.38 | 0.39 | 0.40 | 0.42 |
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC750 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.22 | 0.22 | 0.22 | 0.23 |
| 2 | 0.22 | 0.22 | 0.23 | 0.23 |
| 3 | 0.21 | 0.23 | 0.23 | 0.24 |
| 4 | 0.22 | 0.23 | 0.23 | 0.24 |
| 5 | 0.23 | 0.23 | 0.24 | 0.25 |
| 6 | 0.23 | 0.24 | 0.25 | 0.25 |
| 7 | 0.24 | 0.25 | 0.25 | 0.26 |
| 8 | 0.25 | 0.25 | 0.26 | 0.27 |
| 1 PCS | 2 PCS | 3 PCS | 4 PCS | |
|---|---|---|---|---|
| SC750 V4 quantity | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) | Pressure drop (bar) |
| 1 | 0.22 | 0.22 | 0.22 | 0.23 |
| 2 | 0.22 | 0.22 | 0.23 | 0.23 |
| 3 | 0.21 | 0.23 | 0.23 | 0.24 |
| 4 | 0.22 | 0.23 | 0.23 | 0.24 |
| 5 | 0.23 | 0.23 | 0.24 | 0.25 |
| 6 | 0.23 | 0.24 | 0.25 | 0.25 |
| 7 | 0.24 | 0.25 | 0.25 | 0.26 |
| 8 | 0.25 | 0.25 | 0.26 | 0.27 |
Water requirements — water flow rates
| Water requirements |
|---|
Attention The water required to initially fill the system side cooling loop must be reasonably clean, bacteria-free water (<100 CFU/ml) such as de-mineralized water, reverse osmosis water, de-ionized water, or distilled water. The water must be filtered with an in-line 50 micron filter (approximately 288 mesh). The water must be treated with anti-biological and anti-corrosion measures. Environment quality must be maintain over the lifetime of the system to receive warranty and support on affecting components. For more information please see Water flow rates
|