Water leak problems
Use this information to resolve water leak problems with the Processor Neptune® Core Module.
Suspicious leakage symptoms
- Processor over temperature error indicated by the System Error "!" LED being solid ON at the front of the server 
- The green LED on the leakage sensor will remain solid when there’s no leakage and will blink at 1 Hz if a leak is detected 
- A Lenovo XClarity Controller event may report the following event:- FQXSPUN0019M: Sensor Liquid Leak has transitioned to critical from a less severe state. This event indicates there could be leakage detected. 
 
- If the "leak detect" persists, the affected water loop will need to be replaced 
- Check Lenovo XClarity Controller messages to see if any leakage warnings have been reported. See XClarity Controller events for more information. 
- Remove the node from the chassis, and place it on a stable work surface. See Remove a node from the chassis. 
- Locate the water loop indicated by the message. 
- Use a flashlight to visually inspect the system board for any moisture. 
- Check the water loop for any moisture. 
- If you identify the problem in the steps above, replace the water loop (see Remove the Lenovo Processor Neptune® Core Module).NoteIt is important to visually inspect the bottom of the chassis with a flashlight prior to installing theProcessor Neptune® Core Module into the chassis. 
- After replacing the water loop, run AC cycle and check if the event has been deasserted. 
- If you are unable to identify the problem, run AC cycle and check if the issue still exist. Contact Product Engineer for the further assistance.