FRU preparation and replacement notice

For the PIK rack E5 and rack E6 , system board replacement and water loop replacement require different set of FRUs and procedures. See the following sections for more information.

The following procedures apply to the SD665 V3 nodes below:

1S7D9PCTOLWWJ9013MAD1S7D9PCTOLWWJ9013MAF1S7D9PCTOLWWJ9013MBL
1S7D9PCTOLWWJ9013MA41S7D9PCTOLWWJ9013MB81S7D9PCTOLWWJ9013MBN
1S7D9PCTOLWWJ9013MB41S7D9PCTOLWWJ9013MAM1S7D9PCTOLWWJ9013MB0
1S7D9PCTOLWWJ9013M9W1S7D9PCTOLWWJ9013M9R1S7D9PCTOLWWJ9013M9V
1S7D9PCTOLWWJ9013MB61S7D9PCTOLWWJ9013MB71S7D9PCTOLWWJ9013MAA
1S7D9PCTOLWWJ9013MBF1S7D9PCTOLWWJ9013MAL1S7D9PCTOLWWJ9013MAP
1S7D9PCTOLWWJ9013MB21S7D9PCTOLWWJ9013MB11S7D9PCTOLWWJ9013MBH
1S7D9PCTOLWWJ9013M9Z1S7D9PCTOLWWJ9013MAK1S7D9PCTOLWWJ9013MA8
1S7D9PCTOLWWJ9013M9N1S7D9PCTOLWWJ9013MBB1S7D9PCTOLWWJ9013MAG
1S7D9PCTOLWWJ9013MAV1S7D9PCTOLWWJ9013MBC1S7D9PCTOLWWJ9013MA0
1S7D9PCTOLWWJ9013MAT1S7D9PCTOLWWJ9013M9X1S7D9PCTOLWWJ9013MB9
1S7D9PCTOLWWJ9013MA11S7D9PCTOLWWJ9013MAZ1S7D9PCTOLWWJ9013MBA
1S7D9PCTOLWWJ9013MA21S7D9PCTOLWWJ9013MA71S7D9PCTOLWWJ9013M9T
1S7D9PCTOLWWJ9013MB31S7D9PCTOLWWJ9013MAY1S7D9PCTOLWWJ9013MA5
1S7D9PCTOLWWJ9013MA91S7D9PCTOLWWJ9013MA61S7D9PCTOLWWJ9013MBD
1S7D9PCTOLWWJ9013MBM1S7D9PCTOLWWJ9013MA31S7D9PCTOLWWJ9013MAH
1S7D9PCTOLWWJ9013MAB1S7D9PCTOLWWJ9013M9P1S7D9PCTOLWWJ9013MBE
1S7D9PCTOLWWJ9013MBK1S7D9PCTOLWWJ9013MAX1S7D9PCTOLWWJ9013MBG
1S7D9PCTOLWWJ9013MAC1S7D9PCTOLWWJ9013MAW 
1S7D9PCTOLWWJ9013MAE1S7D9PCTOLWWJ9013M9Y 
1S7D9PCTOLWWJ9013MB51S7D9PCTOLWWJ9019MLZ 

Water loop replacement

Water loop replacement require the following FRUs:

  • SD665 V3 Water Loop Service Kit (The water loop carrier in the Service Kit is reusable, it is recommended to keep it at the facility where the server operates for future replacement needs.)

  • SD665 V3 Water Loop Putty Pad Kit

  • SD665 V3 Conduction Plate Parts

  • VR 2.5 mm Putty Pad

Follow the following procedures to replace the water loop:
  1. Remove the water loop, see Remove the water loop in SD665 V3 User Guide.

  2. Remove the VR conduction plate from the system board, see Step 3 in Remove the system board in SD665 V3 User Guide.

  3. Take the VR conduction plate from SD665 V3 Conduction Plate Parts . With alcohol cleaning pads, wipe off the putty pad from the VR conduction plate.

  4. Paste VR 2.5 mm Putty Pad to the VR conduction plate.

  5. Install the VR conduction plate to the system board, see Step 3 in Install the braided cables.

  6. Install the water loop, see Install the water loop in SD665 V3 User Guide.

System board replacement

System board replacement require the following FRUs:

  • SD665 V3 Water Loop Service Kit (The water loop carrier in the Service Kit is reusable, it is recommended to keep it at the facility where the server operates for future replacement needs.)

  • SD665 V3 Water Loop Putty Pad Kit

  • VR Conduction Plate Parts

  • VR 2.5 mm Putty Pad

  • Shielding cable 1, 2, and 3

Follow the following procedures to replace the system board:
  1. Remove the system board, see Remove the system board in SD665 V3 User Guide.

    Note
    Make sure to save the VR conduction plate and the screws for next step.
  2. With alcohol cleaning pads, wipe off the putty pad from the VR conduction plate. Then, paste the 2.5 mm Putty Pad for VR Conduction Plate (03LA870) to the bottom of the VR conduction plate.

  3. Place the system board into the node, see Step 1 in Install the system board in SD665 V3 User Guide.

  4. Install the shielding cages to the system board, see Install the braided cables.

  5. Install the system board to the node. Complete Step 2, Step 4, and After you finish in Install the system board in SD665 V3 User Guide.