Remove the external LCD diagnostics handset

Follow instructions in this section to remove the external LCD diagnostics handset.

About this task

To avoid possible danger, read and follow the following safety statement.
  • S014
    shock hazard
    CAUTION
    Hazardous voltage, current, and energy levels might be present. Only a qualified service technician is authorized to remove the covers where the label is attached.
  • S017
    moving parts
    CAUTION
    Hazardous moving fan blades nearby.
  • S033
    240VA shock hazard
    CAUTION

    Hazardous energy present. Voltages with hazardous energy might cause heating when shorted with metal, which might result in spattered metal, burns, or both.

Attention

Procedure

Disconnect the external LCD diagnostics handset cable.
  1. Press and hold on the latch on the side of the connector.
  2. Pull to disconnect the cable from the server.
Note
Depending on your configuration, the server and the location of the connector might look different from those shown in the illustrations.
Figure 1. Disconnecting the external LCD diagnostics handset cable



Disconnecting the external LCD diagnostics handset cable

After you finish

  • Install a replacement unit. See Install the external LCD diagnostics handset.

  • If you are instructed to return the component or optional device, follow all packaging instructions, and use any packaging materials for shipping that are supplied to you.