Skip to main content

Environmental specifications

Summary of the environmental specifications of server. Depending on the model, some features might not be available, or some specifications might not apply.

Acoustical noise emissions
The server has the following acoustic noise emissions declaration:
  • Sound power level (LWAd)
    • Idling:
      • Min: 5.4 Bel
      • Typical: 5.4 Bel
      • Max: 5.5 Bel
    • Operating:
      • Min: 5.7 Bel
      • Typical: 6.1 Bel
      • Max: 7.2 Bel
  • Sound pressure level (LpAm):
    • Idling:
      • Min: 43.6 dBA
      • Typical: 43.5 dBA
      • Max: 44.5 dBA
    • Operating:
      • Min: 45.8 dBA
      • Typical: 50.0 dBA
      • Max: 61.1 dBA
Note
  • These sound levels were measured in controlled acoustical environments according to procedures specified by ISO7779 and are reported in accordance with ISO 9296. The operating profile is represented by 80% CPU TDP or 70%/30% storage read/write or 100% GPU workload.
  • The declared acoustic sound levels are based on the specified configurations, which may change depending on configuration/conditions.
    • Min: 1x 80W CPU, 2x 16GB RDIMMs, 1GbE I/O module board, 1 x NVMe M.2 boot drive , 2x SATA SSDs, 2x NVMe M.2 data drives, DC power module board (PMB), no dust filter, rear-to-front fan direction
    • Typical: 1x 80W CPU, 4x 16GB RDIMMs, 10/25GbE I/O module board, 1 x NVMe M.2 boot drive, 1x NVIDIA A2 GPU, 4x NVMe M.2 data drives, no dust filter, DC power module board (PMB), rear-to-front fan direction
    • Max: 1x 100W CPU, 4x 64GB RDIMMs, 10/25GbE I/O module board, 2 x NVMe M.2 boot drives, 2x NVIDIA A2 GPU, 2x NVMe M.2 data drives, DC power module board (PMB), no dust filter, rear-to-front fan direction
  • Government regulations (such as those prescribed by OSHA or European Community Directives) may govern noise level exposure in the workplace and may apply to you and your server installation. The actual sound pressure levels in your installation depend upon a variety of factors, including the number of racks in the installation; the size, materials, and configuration of the room; the noise levels from other equipment; the room ambient temperature, and employee's location in relation to the equipment. Further, compliance with such government regulations depends on a variety of additional factors, including the duration of employees' exposure and whether employees wear hearing protection. Lenovo recommends that you consult with qualified experts in this field to determine whether you are in compliance with the applicable regulations.
Acoustic modes

ThinkEdge SE360 V2 supports three acoustic modes with different acoustic performance.

  • Disabled: The server operates at default fan speeds.

  • Mode 1: The operation of system fans is optimized to lower the overall noise level of the server.
    • Mode 1 supports ambient temperature lower than 35°C.

    • In Mode 1, the server operates with sound pressure level of 50 dBA at 25°C.

    • Performance degradation may occur at heavy workloads.

  • Mode 2: The operation of system fans is optimized to lower the overall noise level of the server further than Mode 1.
    • Mode 2 supports configurations with 4-core or 8-core processor at ambient temperature lower than 35°C.

    • In Mode 2, the server operates with sound pressure level of 45 dBA at 25°C.

    • Performance degradation may occur at heavy workloads.

To change the acoustic mode, enter the Setup Utility and go to System settings > Operating Modes > Acoustic mode.

Ambient temperature management
  • Most of the configurations of SE360 V2 support operating at temperature of 55°C or lower. Specific configuration supports operating at -20°C to 65°C. See Environment for the details of configuration supporting extended operation temperature.

  • The following components can operate at temperature of 55°C or lower and require proper ambient temperature to prevent performance degradation:
    • When one of the following components is installed, keep ambient temperature lower than 45°C for proper operation. If the ambient temperature is over 45°C, performance degradation or throttled event might occur.
      • 16 core processor
      • NVMe M.2 drives
      • NVMe U.3 drives
    • When one of the following drives is installed in Slot 7 to 10 (M.2 Bay 6 to 9) with heavy workload, keep ambient temperature lower than 40°C for proper operation. If the ambient temperature is over 40°C, performance degradation or throttled event might occur.
      • NVMe M.2 drives
      • NVMe U.3 drives
    • When a 300W external power adapter is installed, keep ambient temperature lower than 40°C to prevent performance degradation. If the ambient temperature is over 40°C, performance degradation or throttled event might occur.

  • The following components can operate at temperature of 50°C or lower. Keep ambient temperature lower than 45°C to prevent performance degradation:
    • ThinkSystem NVIDIA A2 16GB PCIe Gen4 Passive GPU
    • ThinkSystem NVIDIA L4 PCIe Gen4 Passive GPU
  • The following components can operate at temperature of 45°C or lower:
    • ThinkSystem Qualcomm Cloud AI 100
    • ThinkSystem Intel Flex 140 GPU
Environment
ThinkEdge SE360 V2 complies with ASHRAE Class A4 specifications. System performance may be impacted when operating temperature is outside AHSARE A4 specification or fan failed condition with ambient temperature over 25°C . ThinkEdge SE360 V2 is supported in the following environment:
  • Air temperature:
    • Operating
      • ASHARE Class H1: 5°C to 25°C (41°F to 77°F); the maximum ambient temperature decreases by 1°C for every 500 m (1640 ft) increase in altitude above 900 m (2,953 ft).
      • ASHARE Class A2: 10°C to 35°C (50°F to 95°F); the maximum ambient temperature decreases by 1°C for every 300 m (984 ft) increase in altitude above 900 m (2,953 ft).
      • ASHARE Class A3: 5°C to 40°C (41°F to 104°F); the maximum ambient temperature decreases by 1°C for every 175m (574 ft) increase in altitude above 900 m (2,953 ft).
      • ASHARE Class A4: 5°C to 45°C (41°F to 113°F); the maximum ambient temperature decreases by 1°C for every 125m (410 ft) increase in altitude above 900 m (2,953 ft).
    • Server off: 5°C to 45°C (41°F to 113°F)
    • Extended operation temperature (with limited configuration):
      • Server on: -20°C to 65°C (-4°F to 149°F), to 70°C for 16 hours(158°F)

      • Server off: -20°C to 65°C (-4°F to 149°F)

      Note
      The configurations support extended operation temperature require:
      • 12 core processor

      • Fans with rear-to-front air flow direction

      • One of the following electrical input:

        • Dual 12-48V variable DC power source input

        • Single 500W (230V/115V) AC power source input

      • All installed DIMMs are RDIMM Extended Temperature

      • All installed M.2 drives are M.2 SSD (Industrial)

      • No GPU adapter or Ethernet adapter installed

    • Shipment/storage: -40°C to 65°C (-40°F to 140°F)
  • Maximum altitude: 3050 m (10,000 ft)

  • Relative Humidity (non-condensing):

    • Operating: 8% to 90%, maximum dew point: 24°C (75.2°F)

    • Shipment/storage: 8% to 90%, maximum dew point : 27°C (80.6°F)

    • Non-operating (unpacked) storage can pass the following condition: 5% to 95% at 38.7°C (101.7°F) maximum dry-bulb temperature for 48 hrs.

  • Particulate contamination
    • SE360 V2 supports a dust filter installed at rear of the node. The dust filter has a Minimum Efficiency Rating Value (MERV) of 5, per ASHRAE 52.2-2017 / 80% Average Arrestance per ASHRAE 52.1-1992.

    • SE360 V2 2U2N Enclosure supports a set of dust filters installed in the front shipping bracket. The dust filter set has a Minimum Efficiency Rating Value (MERV) of 5, per ASHRAE 52.2-2017 / 80% Average Arrestance per ASHRAE 52.1-1992.

    • SE360 V2 complies with IP3X Ingress Protection per ANSI/IEC60529-2020 Degrees of Protection Provided by Enclosures (IP Code)

      Note
      The configurations with one of the following PCIe adapters do not comply with IP3X standard:
      • ThinkSystem Qualcomm Cloud AI 100

      • ThinkSystem Intel Flex 140 12GB Gen4 Passive GPU

      • ThinkSystem Intel X710-T4L 10GBase-T 4-Port PCIe Ethernet Adapter

      • ThinkSystem Intel E810-DA2 10/25GbE SFP28 2-Port PCIe Ethernet Adapter

    Attention
    Airborne particulates and reactive gases acting alone or in combination with other environmental factors such as humidity or temperature might pose a risk to the server. For information about the limits for particulates and gases, see Particulate contamination.