ThinkSystem SR665 V3 complies with ASHRAE Class A2 specifications with most configurations, and depending on the hardware configuration, also complies with ASHRAE Class A3 and Class A4 specifications. System performance may be impacted when the operating temperature is outside ASHRAE A2 specification. Depending on the hardware configuration, SR665 V3 server also complies with ASHRAE Class H1 specification. System performance may be impacted when the operating temperature is outside ASHRAE H1 specification. The restrictions to ASHRAE support are as follows (cooling by air): The ambient temperature must be limited to 35 °C or lower if the server has any of the following components: Broadcom 57416 10GBASE-T 2-port OCP Broadcom 57454 10GBASE-T 4-port OCP Network interface cards (NICs) at a rate greater than or equal to 100 GB Parts with AOC and at the rate of 25 GB
The ambient temperature must be limited to 30 °C or lower if the server has any of the following components: 24 x 2.5" or 12 x 3.5" front bay with middle or rear bay GPU (except front 24 x 2.5" configurations and configurations with Group E processors) Parts with AOC and at a rate greater than 25 GB 9654(P)/9554(P)/9174F/9754/9734/9684X/9555/9655 processors using performance heat sinks in a front 8 x 2.5"/8 x 3.5"/16 x 2.5" standard configuration. Group E processors using advanced heat sinks in a front 12 x 3.5"/24 x 2.5" configuration without middle/rear bay
The ambient temperature must be limited to 25 °C or lower if the server has any of the following components: 9274F/9374F/9474F/9575F using performance heat sinks in a front 8 x 2.5"/8 x 3.5"/16 x 2.5" standard configuration 9654(P)/9554(P)/9174F/9754/9734/9555/9655 using performance heat sinks in a front 24 x 2.5" configuration without middle/rear bay 9654(P)/9554(P)/9174F/9754/9734/9684X/9555/9655 in a front 8 x 2.5"/8 x 3.5"/16 x 2.5" + GPU configuration 24 x 2.5" front bay + GPU Gen5 7.68 TB or larger capacity NVMe in a configuration with middle/rear bay Group A (240 W < cTDP ≤ 300 W) processor in a configuration with middle/rear bay ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1 H100 NVL GPU adapter
The restrictions to ASHRAE support are as follows (cooling by Direct Water Cooling Module (DWCM)): The ambient temperature must be limited to 35 °C or lower if the server has any of the following components: Broadcom 57416 10GBASE-T 2-port OCP Broadcom 57454 10GBASE-T 4-port OCP Network interface cards (NICs) at a rate greater than or equal to 100 GB Parts with AOC and at the rate of 25 GB
The ambient temperature must be limited to 30 °C or lower if the server has any of the following components: Gen5 7.68 TB or larger capacity NVMe in a configuration with middle/rear bay three 300 W or 350 W GPUs installed in a configuration with 16 x 2.5" or 8 x 3.5" front bay three 300 W GPUs installed in an 8 x 2.5" + FIO or 16 x 2.5" + FIO configuration three H100/L40S GPUs installed in a configuration with 24 x 2.5" front bay or in an 8 x 2.5" + FIO or 16 x 2.5" + FIO configuration ThinkSystem 96GB TruDDR5 4800MHz (2Rx4) RDIMM-A installed in a GPU configuration ThinkSystem 128GB TruDDR5 4800MHz (4Rx4) 3DS RDIMM-A v1 installed in a GPU configuration ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1 installed in a standard configuration with standard fans or a storage configuration with 24 x 2.5" front bay and standard fans parts with AOC and at a rate greater than 25 GB H100 NVL GPU adapter
The ambient temperature must be limited to 25 °C or lower if the server has any of the following components: three A40 or L40 GPUs installed in a configuration with 24 x 2.5" front bay or in an 8 x 2.5" + FIO or 16 x 2.5" + FIO configuration ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1 installed in a configuration with 12 x 3.5" front bay and performance fans
For detailed thermal information, see Thermal rules. When the ambient temperature is greater than the supported max temperature (ASHARE A4 45°C), the server will shut down. The server will not power on again until the ambient temperature falls within the supported temperature range. Air temperature: Maximum altitude: 3,050 m (10,000 ft) Relative Humidity (non-condensing):
|