Install the system board retention clip

Follow instructions in this section to install the system board retention clip. The procedure must be executed by a trained technician.

About this task

Important

Removing and installing this component requires trained technicians. Do not attempt to remove or install it without proper training.

Attention
  • Read Installation Guidelines and Safety inspection checklist to ensure that you work safely.
  • Touch the static-protective package that contains the component to any unpainted metal surface on the server; then, remove it from the package and place it on a static-protective surface.
Note
Make sure you have a torque screwdriver available to properly replace the component.

Procedure

  1. Loosen the four screws located on the front of the system board.
    Figure 1. Screw removal
    Screw removal
  2. Slightly lift the system board. Then, slide the retention clip onto the system board and insert it into the front fan control board connector until it is securely seated.
    Figure 2. System board retention clip installation
    System board retention clip installation
  3. Set the torque screwdriver to 8 inch-pounds. Then, fasten the four screws located on the front of the system board.
    Figure 3. Screw installation
    Screw installation

After you finish

  1. Reinstall the heat sinks. See Install a processor and heat sink.
  2. Reinstall the compute tray. See Install the compute tray.
  3. Ensure that all components have been reassembled correctly and that no tools or loose screws are left inside the server.
  4. Reinstall the system shuttle. See Install the system shuttle.
  5. Complete the parts replacement. See Complete the parts replacement.