FQXSPCA0001J : Numeric sensor [NumericSensorElementName] going low (lower non-critical) has asserted.

Numeric sensor [NumericSensorElementName] going low (lower non-critical) has asserted.

This message is for the use case when an implementation has detected a Lower Non-critical sensor going low has asserted.

Severity

Warning

Alert Category

Warning - Temperature

Serviceable

Yes

CIM Information

Prefix:PLAT

and ID:0476

SNMP Trap ID

12

Automatically Notify Support

No

User Action

Complete the following steps:

  1. Ensure the room and inlet water temperature/flow rate to the rack are within server environmental specification to adjust the temperature.
  2. If the problem issue still exist, check XCC Web GUI to check the temperature value is still higher than system spec. If warning is seen post service action on GPU then it is possible the thermal interface material take time to melt and the warnings are expected to deassert after a day of normal operation.
  3. Please contact Lenovo support.
  4. If the message persists more than 24 hours after GPU is replaced, contact Lenovo service