FQXSPCA0011N : Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has asserted.
Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has asserted.
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor going high has asserted.
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Action
Complete the following steps until the problem is solved:
- If the sensor is "Ambient Temp":
- Make sure the data center Temperature environment is within 50°C degree.
- Make sure there is no hot air in front of the affected system.
- If the problem persists, collect service data log from the XCC WebGUI and contact Lenovo Support.
- If the sensor is "CPU 1 DTS" or "CPU 2 DTS":
- Check the XCC event log for any fan or cooling related issues and fix them first.
- Make sure there is no hot air in front of the affected system.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are correctly installed in place and keep clean.
- Make sure that the room temperature meets operating specifications.
- Upgrade all system firmware and chassis firmware (if applicable) to the latest level. NOTE: If the device is part of a cluster solution, verify that the latest level of code is supported by the cluster solution before the update.
- If the problem persists, collect service data log from the XCC WebGUI and contact Lenovo Support.