Install the integrated diagnostics panel

Follow instructions in this section to install the integrated diagnostics panel. The procedure must be executed by a trained technician.

About this task

Attention
  • Read Installation Guidelines and Safety inspection checklist to ensure that you work safely.
  • Touch the static-protective package that contains the component to any unpainted metal surface on the server; then, remove it from the package and place it on a static-protective surface.

Procedure

  1. If necessary, attach the labels to both ends of the cable.
    1. Attach the white space portion of the label to one end of the cable.
    2. Wrap the label around the cable and attach it to the white space portion.
    3. Repeat to attach the other label to the opposite end of the cable.
    Figure 1. Label application
    Label application
    Note
    See the table below to identify the corresponding label for the cable.
    FromToLabel
    Integrated diagnostics panel cableSystem board: Integrated diagnostics panel (Front I/O) connector
    • PANEL
    • FRONT IO 2
  2. Install the integrated diagnostics panel.
    1. Connect the cable to the integrated diagnostics panel.
    2. Align the integrated diagnostics panel with the slot at the front of the NVMe drive and PCIe switch board cage, and slide it in.
    Figure 2. Integrated diagnostics panel installation
    Integrated diagnostics panel installation

After you finish

  1. Reinstall the front fan cage. See Install the front fan cage.
  2. Push the system shuttle fully into the chassis.
    1. Lift the two lock latches on both sides of the shuttle.
    2. Slide the shuttle into the chassis.
    3. Push the shuttle fully into the chassis.
    4. Rotate the two release levers until they lock into place.
    Figure 3. System shuttle installation
    System shuttle installation

    System shuttle installation
  3. Complete the parts replacement. See Complete the parts replacement.