FQXST0040M : The sensors monitored a temperature or voltage in the failure range. When the problem is resolved, event 47 is logged for the component that logged event 40.

The sensors monitored a temperature or voltage in the failure range. When the problem is resolved, event 47 is logged for the component that logged event 40.

Severity

Critical

Serviceable with log

No

Automatically Notify Support

No

User Action

  1. Check that the storage system's fans are running.
  2. Check that the ambient temperature is not too warm. The enclosure operating range is 5-40\ufffd C (41\ufffd F-104\ufffd F).
  3. Check for any obstructions to the air flow.
  4. Check that there is a module or blank filler in every module bay in the enclosure.
  5. If none of the above explanations apply, replace the disk or controller module that logged the error.