Environmental specifications
Summary of the environmental specifications of the server. Depending on the model, some features might not be available, or some specifications might not apply.
Acoustical noise emissions
Acoustical noise emissions | ||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
The server has the following acoustic noise emissions declaration:
Note
|
Ambient temperature management
Ambient temperature management |
---|
The server is supported in the following environment:
|
Environment
Environment |
---|
ThinkSystem SR630 V3 complies with ASHRAE Class A2 specifications. System performance may be affected when operating temperature is outside of AHSARE A2 specification.
Note The server is designed for standard data center environment and recommended to be placed in industrial data centers. When the ambient temperature is greater than the supported max temperature (ASHARE A4 45°C), the server will shut down. The server will not power on again until the ambient temperature falls within the supported temperature range. Depending on hardware configurations, the server complies with ASHRAE Class H1, A2, A3, or A4 specifications with certain thermal restrictions. System performance may be impacted when operating temperature is out of permitted conditions. The restrictions to ASHRAE support are as follows (cooling by air or Liquid to Air Module (L2AM)) :
The restrictions to ASHRAE support are as follows (cooling by Direct Water Cooling Module (DWCM)) :
Note For more thermal information about 128/256 GB RDIMMs, see |
Water requirements
Water requirements | ||||||||
---|---|---|---|---|---|---|---|---|
ThinkSystem SR630 V3 is supported in the following environment:
Note The water required to initially fill the system side cooling loop must be reasonably clean, bacteria-free water (<100 CFU/ml) such as de-mineralized water, reverse osmosis water, de-ionized water, or distilled water. The water must be filtered with an in-line 50 micron filter (approximately 288 mesh). The water must be treated with anti-biological and anti-corrosion measures. |