FQXSPCA0009M : Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
This message is for the use case when an implementation has detected an Upper Critical sensor going high has asserted.
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Action
Complete the following steps:
- Check the event log of system management module and XClarity Controller for any cooling related issue.
- Make sure CDU supply water temperature and flow rate per tray is within operating specifications.
- Make sure waterloop assembly and maifold are installed correctly.
- Make sure that the room temperature is within operating specifications.
- If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
Give documentation feedback