FQXSPPU0001N : An Over-Temperature Condition has been detected on [ProcessorElementName].
An Over-Temperature Condition has been detected on [ProcessorElementName].
This message is for the use case when an implementation has detected an Over-Temperature Condition Detected for Processor.
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Action
Complete the following steps:
- Check the event log of system management module and XClarity Controller for any cooling related issue.
- Make sure CDU supply water temperature and flow rate per tray is within operating specifications.
- Make sure waterloop assembly and maifold are installed correctly.
- Make sure that the room temperature is within operating specifications.
- If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.