FQXSPCA0017M : Sensor [SensorElementName] has transitioned to critical from a less severe state.
Sensor [SensorElementName] has transitioned to critical from a less severe state.
This message is for the use case when an implementation has detected a Sensor transitioned to critical from less severe.
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Action
Complete the following steps:
- Check the event log of system management module and XClarity Controller for any cooling related issue.
- Make sure CDU supply water temperature and flow rate per tray is within operating specifications.
- Make sure waterloop assembly and maifold are installed correctly.
- Make sure that the room temperature is within operating specifications.
- If the problem persists, contact Lenovo Support.