ThinkSystem SR650 V3 complies with ASHRAE Class A2 specifications with most configurations, and depending on the hardware configuration, also complies with ASHRAE Class A3 and Class A4 specifications. System performance may be impacted when the operating temperature is outside ASHRAE A2 specification. Depending on the hardware configuration, SR650 V3 server also complies with ASHRAE Class H1 specification. System performance may be impacted when the operating temperature is outside ASHRAE H1 specification. The restrictions to ASHRAE support are as follows (cooling by air): The ambient temperature must be limited to 35 °C or lower if the server has any of the following components: Broadcom 57416 10GBASE-T 2-port OCP Broadcom 57454 10GBASE-T 4-port OCP PCIe network interface card (NIC) at a rate greater than or equal to 100 GB Part with AOC and at the rate of 40 GB
The ambient temperature must be limited to 30 °C or lower if the server has any of the following components: 24 x 2.5" or 12 x 3.5" front bay with middle bay or rear bay GPU adapters 256 GB 3DS RDIMM 350 W processor part with AOC and at a rate greater than 40 GB 5600 MHz RDIMMs with capacity greater than or equal to 96 GB - ThinkSystem 96GB TruDDR5 4800MHz (2Rx4) RDIMM
ThinkSystem 128GB TruDDR5 4800MHz (4Rx4) 3DS RDIMM v1 4800 MHz 256 GB RDIMMs (except ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM v1)
The ambient temperature must be limited to 25 °C or lower if the server has any of the following components or configurations: 350 W processor installed in the chassis with 24 x 2.5" or 12 x 3.5" front drives 350 W processor installed in the 16 x 2.5" + FIO non-GPU configuration processor (270 W <=TDP <= 300 W) installed in the chassis with middle or rear drives GPU adapter installed in the chassis with 24 x 2.5" front drives GPU adapter and processor with TDP rating greater than 300 W installed in the chassis with 16 x 2.5" or 8 x 3.5" front drives drives larger than 3.84 TB installed in Gen 5 rear or middle NVMe drive bays 36 NVMe configuration 16 x 2.5" + FIO GPU configuration ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM v1 ThinkSystem 96GB TruDDR5 4800MHz (2Rx4) RDIMM and ThinkSystem 128GB TruDDR5 5600MHz (2Rx4) RDIMM installed in the following configurations: 12 x 3.5" configurations including processors with TDP greater than 250 W and less than or equal to 300 W 12 x 3.5" + middle/rear drive bay configurations including processors with TDP greater than 250 W and less than or equal to 270 W
the following NVMe SSDs installed in the front 12 x 3.5" SAS/SATA + middle 8 x 2.5" NVMe or front 12 x 3.5" SAS/SATA + rear 4 x 2.5" NVMe configuration: ThinkSystem 2.5" U.2 P5336 61.44TB Read Intensive NVMe PCIe 4.0 x4 HS SSD ThinkSystem 2.5" U.2 P5336 30.72TB Read Intensive NVMe PCIe 4.0 x4 HS SSD ThinkSystem 2.5" U.2 P5336 15.36TB Read Intensive NVMe PCIe 4.0 x4 HS SSD
H100 NVL GPU adapter
The restrictions to ASHRAE support are as follows (cooling by Direct Water Cooling Module (DWCM)): The ambient temperature must be limited to 35 °C or lower if the server has any of the following components or configurations: Broadcom 57416 10GBASE-T 2-port OCP Broadcom 57454 10GBASE-T 4-port OCP PCIe network interface card (NIC) at a rate greater than or equal to 100 GB Part with AOC and at the rate of 40 GB GPU adapters (< 300 W) installed in 8 x 3.5" or 16 x 2.5" configurations 64 GB < DIMM < 256 GB 8 x 2.5" GPU configuration storage configuration without middle or rear NVMe backplane
The ambient temperature must be limited to 30 °C or lower if the server has any of the following components: 256 GB 3DS RDIMM part with AOC and at a rate greater than 40 GB GPU adapters (>= 300 W) installed in 8 x 3.5" or 16 x 2.5" configurations three A40 GPU adapters installed in 24 x 2.5" configurations storage configuration with middle or rear NVMe backplane 5600 MHz RDIMMs with capacity greater than or equal to 96 GB - ThinkSystem 96GB TruDDR5 4800MHz (2Rx4) RDIMM
ThinkSystem 128GB TruDDR5 4800MHz (4Rx4) 3DS RDIMM v1 4800 MHz 256 GB RDIMMs (except ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM v1) H100 NVL GPU adapter
The ambient temperature must be limited to 25 °C or lower if the server has any of the following components: three H800/H100 GPU adapters installed in 24 x 2.5" configurations three H800/H100 GPU adapters installed in 16 x 2.5" + FIO configurations ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM v1 the following NVMe SSDs installed in the front 12 x 3.5" SAS/SATA + middle 8 x 2.5" NVMe or front 12 x 3.5" SAS/SATA + rear 4 x 2.5" NVMe configuration: ThinkSystem 2.5" U.2 P5336 61.44TB Read Intensive NVMe PCIe 4.0 x4 HS SSD ThinkSystem 2.5" U.2 P5336 30.72TB Read Intensive NVMe PCIe 4.0 x4 HS SSD ThinkSystem 2.5" U.2 P5336 15.36TB Read Intensive NVMe PCIe 4.0 x4 HS SSD
For detailed thermal information, see Thermal rules. When the ambient temperature is greater than the supported max temperature (ASHARE A4 45°C), the server will shut down. The server will not power on again until the ambient temperature falls within the supported temperature range. Air temperature: Maximum altitude: 3,050 m (10,000 ft) Relative Humidity (non-condensing):
|