Configuration

Configuration tabs settings are used to manage FPC module.

Figure 1. Configuration
Configuration
There are eight sections:
  • Firmware Update

  • SMTP

  • SNMP

  • PEF

  • Network Configuration

  • Time Setting

  • User Account

  • Account Security

  • Web Certificate

Note
By pressing hardware reset button for more than 4 seconds, all settings (except Time Setting) can be restored to out-of-factory default settings.

All settings, except time setting, in the configuration tab can be restored to out-of-factory default settings through coin battery removal or by pressing hardware reset button for more than 4s.

Complete the following steps to remove the coin battery:
  1. Pull FPC module out of the chassis.

  2. Remove coin battery from FPC module.

  3. Insert FPC module without battery back to chassis, boot up, and wait for FPC to reboot.

  4. The following sings can be observed during FPC boot up and reboot.

    1. Power LED lit on.

    2. Heartbeat LED blinks for 0.3 seconds on and 3.8 seconds off.

    3. Checklog LED lit on due to lack of battery

    4. FPC then reboot and have fan spin up, Power LED lit, Heartbeat LED blinks and Checklog LED on again.

  5. After observing Checklog LED lit up again after FPC reboot, pull FPC module out of the chassis.

  6. Install the battery back to FPC module.

  7. Insert FPC module with battery back to chassis.