ThinkSystem SR635 V3 complies with ASHRAE Class A2 specifications with most configurations, and depending on the hardware configuration, also complies with ASHRAE Class A3 and Class A4 specifications. System performance may be impacted when the operating temperature is outside ASHRAE A2 specification. Depending on the hardware configuration, SR635 V3 server also complies with ASHRAE Class H1 specification. System performance may be impacted when the operating temperature is outside ASHRAE H1 specification. The restrictions to ASHRAE support are as follows (cooling by air or Liquid to Air Module (L2AM)):The ambient temperature must be limited to 45 °C or lower (TDP < 240W) if the server meets the following conditions: Installed with any TruDDR5 memory DIMM (64 GB or below) Without 2.5" NVMe, NVMe M.2 or NVMe AIC drives Without rear drives or 7mm drives Without GPU adapters Without any PCIe network interface cards (NICs) at a rate equal to or above 25 GB Without any parts with AOC and at a rate equal to or above 25 GB Without closed loop heat sink
The ambient temperature must be limited to 40 °C or lower (TDP <300 W) if the server meets the following conditions: Installed with any TruDDR5 memory DIMM (64 GB or below) Without 2.5" NVMe, NVMe M.2 or NVMe AIC drives Without rear drives or 7mm drives Without GPU adapters Without any PCIe network interface cards (NICs) at a rate equal to or above 25 GB Without any parts with AOC and at a rate equal to or above 25 GB Without closed loop heat sink
The ambient temperature must be limited to 35 °C or lower (320 W ≤TDP ≤ 400 W) if the server has any of the following components: TruDDR5 memory 128 GB DIMM ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v2 NVMe, NVMe M.2 or NVMe AIC drives Broadcom 57416 10GBASE-T 2-port OCP Broadcom 57454 10GBASE-T 4-port OCP PCIe network interface cards (NICs) at a rate equal to or above 25 GB Parts with AOC and at a rate equal to or above 25 GB GPU adapters
The ambient temperature must be limited to 30 °C or lower if the server has any of the following components: Rear drives EDSFF drives Parts with AOC and at a rate higher than 25 GB PCIe network interface cards (NICs) at a rate higher than 25 GB ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1
The restrictions to ASHRAE support are as follows (cooling by Direct Water Cooling Module (DWCM)):The ambient temperature must be limited to 45 °C or lower (TDP < 240W) if the server meets the following conditions: Installed with any TruDDR5 memory DIMM (64 GB or below) Without 2.5" NVMe, NVMe M.2 or NVMe AIC drives Without rear drives or 7mm drives Without GPU adapters Without any PCIe network interface cards (NICs) at a rate equal to or above 25 GB Without any parts with AOC and at a rate equal to or above 25 GB
The ambient temperature must be limited to 40 °C or lower (TDP <300 W) if the server meets the following conditions: Installed with any TruDDR5 memory DIMM (64 GB or below) Without 2.5" NVMe, NVMe M.2 or NVMe AIC drives Without rear drives or 7mm drives Without GPU adapters Without any PCIe network interface cards (NICs) at a rate equal to or above 25 GB Without any parts with AOC and at a rate equal to or above 25 GB
The ambient temperature must be limited to 35 °C or lower (320 W ≤TDP ≤ 400 W) if the server has any of the following components: TruDDR5 memory 128 GB DIMM (4800MHz/5600MHz/6400MHz) ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v2 NVMe, NVMe M.2 or NVMe AIC drives Broadcom 57416 10GBASE-T 2-port OCP Broadcom 57454 10GBASE-T 4-port OCP PCIe network interface cards (NICs) at a rate equal to or above 25 GB Parts with AOC and at a rate equal to or above 25 GB GPU adapters
The ambient temperature must be limited to 30 °C or lower if the server has any of the following components: Rear drives EDSFF drives Parts with AOC and at a rate higher than 25 GB PCIe network interface cards (NICs) at a rate higher than 25 GB ThinkSystem 256GB TruDDR5 4800MHz (8Rx4) 3DS RDIMM-A v1
For detailed thermal information, see Thermal rules. When the ambient temperature is greater than the supported max temperature (ASHARE A4 45°C), the server will shut down. The server will not power on again until the ambient temperature falls within the supported temperature range. |