80010901-3701ffff : Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
The inlet 1 temperature has exceeded its specified threshold. The compute node has attempted a soft shutdown.
May also be shown as 800109013701ffff or 0x800109013701ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.
Give documentation feedback