80070101-030401ff : Sensor CPU 4 Overtemp has transitioned from normal to non-critical state.
Sensor CPU 4 Overtemp has transitioned from normal to non-critical state.
The temperature of microprocessor 4 has exceeded its specified threshold.
May also be shown as 80070101030401ff or 0x80070101030401ff
Severity
Warning
Alert Category
Warning - Temperature
Serviceable
Yes
SNMP Trap ID
12
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.
Give documentation feedback