806f0107-0303ffff : An over-temperature condition has been detected on [ProcessorElementName].
An over-temperature condition has been detected on [ProcessorElementName].
The temperature of microprocessor 3 has exceeded the critical level, causing a hard shutdown of the compute node.
May also be shown as 806f01070303ffff or 0x806f01070303ffff
Severity
Error
Alert Category
Critical - Temperature
Serviceable
Yes
SNMP Trap ID
0
Automatically Notify Support
No
User Response
Complete the following steps until the problem is solved:
- Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
- Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly installed.
- Make sure that the room temperature is within operating specifications.
- Make sure that the microprocessor heat sink is securely installed.
- Make sure that the microprocessor heat sink is installed correctly and the thermal material is correctly applied.
- Replace microprocessor 3.